THX9321 PRESTIGE
®
2.0 AND THX9421 PRESTIGE
®
IAQ WITH EIM
51
68-0311—02
6040
Remote Setback -
Standby Heat
Setpoint
50° F to 70° F
64° F
Commercial Yes
Remote Setback requires an EIM
(Equipment Interface Module).
During occupied periods, the occupancy
sensor tells the thermostat to go to
STANDBY (setback settings) when no one
is in the room. If someone is in the room,
then it follows the settings of the occupied
period. The occupancy sensor is ignored
during unoccupied periods.
If the thermostat is setup for non-
programmable, the occupancy sensor tells
the thermostat to go to STANDBY settings
when no one is in the room. If someone is
in the room, then it follows the settings set
by the user.
6050
What Terminals are
Wired to the Full
Drain Pan Alert Dry
Contact?
None
S1
S2
S3
S4
None
Both
Yes
Dry Contact Alerts require an EIM
(Equipment Interface Module).
6060
Full Drain Pan Alert
Dry Contact Setup
Normally Open
Normally Closed
Normally Open Both
Yes
Dry Contact Alerts require an EIM
(Equipment Interface Module).
Choose an option appropriate for the type
of device installed.
Normally Open: The Dry Contact device is
normally open and will close when the
device detects the drain pan is full.
Normally Closed: The Dry Contact device is
normally closed and will open when the
device detects the drain pan is full.
6070
What Terminals are
Wired to the Dirty
Filter Alert Dry
Contact?
None
S1
S2
S3
S4
None
Both
Yes
Dry Contact Alerts require an EIM
(Equipment Interface Module).
6080
Dirty Filter Alert
Dry Contact Setup
Normally Open
Normally Closed
Normally Open Both
Yes
Dry Contact Alerts require an EIM
(Equipment Interface Module).
Choose an option appropriate for the type
of device installed:
Normally Open: The Dry Contact device is
normally open and will close when the
device detects a dirty filter.
Normally Closed: The Dry Contact device is
normally closed and will open when the
device detects a dirty filter.
6090
What Terminals are
Wired to the Water
Leak Alert Dry
Contact?
None
S1
S2
S3
S4
None
Both
Yes
Dry Contact Alerts require an EIM
(Equipment Interface Module).
Table 4. Installer Setup (ISU) Table. (Continued)
ISU
Number
Installer Setup
Name
Settings
Default
Residential,
Commercial
or Both
Requires
EIM
Notes