OMMISSIONING
6.4
Maintenance
In normal conditions, the drive is maintenance-free. However, regular maintenance is recom-
mended to ensure a trouble-free operation and a long lifetime of the drive. We recommend to
follow the table below for maintenance intervals.
NOTE:
Because of capacitor type (thin film capacitors), reforming of capacitors is not neces-
sary.
Maintenance interval
Maintenance action
Regularly and according to
general maintenance interval
•
Check tightening torques of terminals
•
Check filters
6...24 months (depending on
environment)
•
Check input and output terminals and
control I/O terminals.
•
Check operation of cooling fan
•
Check for corrosion on terminals, bus-
bars and other surfaces
•
Check door filters in case of cabinet
installation
24 months
•
Clean heatsink and cooling tunnel
3...6 years
•
Change internal IP54 fan
6...10 years
•
Change main fan