• 19
M
OUNTING
Note that if several units are mounted above each
other the required free space equals C + D (see Fig-
ure 11.). Moreover, the outlet air used for cooling by
the lower unit must be directed away from the air in-
take of the upper unit by means of e.g. a piece of met-
al plate fixed to cabinet wall between the drives as
shown in Figure 11.
Figure 11. Installation space when drives are
mounted on top of each other
Table 12. Required cooling air
Type
Cooling air required
[m
3
/h]
MR4
45
MR5
75
MR6
190
MR7
185
MR8
335
MR9
621
C+D
FRONT
SIDE