Honeywell
• 23
P
OWER
CABLING
4.1.1.2
Cable and fuse sizes, frames MR7 to MR9
The recommended fuse types are gG/gL (IEC 60269-1) or class T (UL & CSA). The fuse volt-
age rating should be selected according to the supply network. The final selection should be
made according to local regulations, cable installation conditions and cable specification. Big-
ger fuses than what is recommended below shall not be used.
Check that the fuse operating time is less than 0.4 seconds. Operating time depends on used
fuse type and impedance of the supply circuit. Consult the factory about faster fuses. Honey-
well offers recommendations also for high speed J (UL & CSA ), aR (UL recognized, IEC
60269-4) and gS (IEC 60269-4) fuse ranges.
Table 15. Cable and fuse sizes
The cable dimensioning is based on the criteria of the International Standard IEC60364-5-52:Cables
must be PVC-isolated; Max ambient tempe30°C, max temperature of cable s70°C; Use
only cables with concentric copper shield; Max number of parallel cables is 9.
When using cables in parallel,
NOTE HOWEVER
that the requirements of both the cross-sectional
area and the max number of cables must be observed.
For important information on the requirements of the earthing conductor, see chapter Earthing and earth
fault protection of the standard.
For the correction factors for each temperature, see International Standard IEC60364-5-52.
Frame
Type
I
L
[A]
Fuse
(gG/gL)
[A]
Mains and
motor cable
Cu [mm
2
]
Terminal cable size
Main terminal
Earth
terminal
MR7
230 18P
400 37P
75.0
72.0
80
3*35+16 (Cu)
3*50+16 (Al)
6-70 mm
2
Cu/Al 6-70 mm
2
230 22P
400 45P
88.0
87.0
100
3*35+16 (Cu)
3*70+21 (Al)
6-70 mm
2
Cu/Al 6-70 mm
2
230 30P
400 55P
105.0
105.0
125
3*50+25 (Cu)
3*70+21 (Al)
6-70 mm
2
Cu/Al 6-70 mm
2
MR8
230 37P
400 75P
143.0
140.0
160
3*70+35 (Cu)
3*95+29 (Al)
Bolt size M8
Bolt size M8
230 45P
400 90P
170.0
170.0
200
3*95+50 (Cu)
3*150+41 (Al)
Bolt size M8
Bolt size M8
230 55P
400 110
208.0
205.0
250
3*120+70 (Cu)
3*185+57 (Al)
Bolt size M8
Bolt size M8
MR9
230 75P
400 132
261.0
261.0
315
3*185+95 (Cu)
2*3*120+41
(Al)
Bolt size M8
Bolt size M8
230 90P
400 160
310.0
310.0
350
2*3*95+50 (Cu)
2*3*120+41
(Al)
Bolt size M8
Bolt size M8