Cooling
The drives produce heat in operation and are cooled down by air circulated by a fan. Enough
free space shall therefore be left around the drive to ensure sufficient air circulation and cooling.
Different acts of maintenance also require certain amount of free space.
Make sure that the temperature of the cooling air does not exceed the maximum ambient tem-
perature of the converter.
Table 11. Min. clearances around drive
Figure 10. Installation space
A = clearance around the freq. converter (see also B)
B = distance from one drive to another or distance to cabinet wall
C = free space above the drive
D = free space underneath the drive
Min clearance [mm]
Type
A
*
*. Min clearances A and B for
drives with IP54 enclosure is 0
mm.
B
*
C
D
MR4
20
20
100
50
MR5
20
20
120
60
MR6
20
20
160
80
MR7
20
20
250
100
MR8
20
20
300
150
MR9
20
20
350
200
C
A
NK5_ 2
D
B
A
B