P
OWER
CABLING
*360º earthing of the shield with cable glands in motor end needed for EMC level C2.
4 = Screened cable equipped with compact low-impedance shield (JAMAK, SAB/ÖZCuY-
O or similar).
Figure 13.
NOTE
: The EMC requirements are fulfilled at factory defaults of switching frequencies (all
frames).
NOTE:
If safety switch is connected the EMC protection shall be continuous over the whole ca-
ble installation.
4.1
UL standards on cabling
To meet the UL (Underwriters Laboratories) regulations, use a UL-approved copper cable with
a minimum heat-resistance of +60/75°C. Use Class 1 wire only.
The units are suitable for use on a circuit capable of delivering not more than 100,000 rms sym-
metrical amperes, 600V maximum.
4.1.1
Cable dimensioning and selection
Table 14 shows the minimum dimensions of the Cu/Al-cables and the corresponding fuse siz-
es. Recommended fuse types are gG/gL.
These instructions apply only to cases with one motor and one cable connection from the drive
to the motor. In any other case, ask the factory for more information.
PE conductor
and shield
PE conductors
Shield