IGSMHS Installation and Setup Guide
3-14
PROMPTS
ZONE
TRIG.
4204/
2-4204
ENTRY
OPTIONS
DESCRIPTION
NOTE:
The next prompt only appears if the Comm Path Choice is IP&GSM, or IP.
20
IP Flt Time
(01 mins)_
[00-99]
In the event there is a loss of contact with the
network over the Ethernet connection, enter the
time delay (in minutes) before the IGSMHS
notifies the central station. IP failure will
always be sent to the central station as Primary
Communication Path Failure.
UL:
Must be one (01) minute.
NOTE:
The next prompt only appears if the Comm Path Choice is IP&GSM, or GSM.
21
GSM Flt Time
(01 mins)_
[00-99]
In the event the module detects a communica-
tion path failure, enter the time delay (in
minutes) before the IGSMHS notifies the
central station. A GSM failure will always be
sent to the central station as Secondary
Communication Path Failure.
UL:
Must be one (01) minute.
NOTE:
The next prompt only appears if the Comm Path Choice is IP&GSM.
22
Notify Panel Of_
(Both IP&GSM
Flts)_
[Both IP and
GSM Faults]
[Neither
fault]
If "Both IP and GSM Faults" is selected, the
device will only notify the control panel if both
communication paths fail, but will always send
notification of either failure to the central
station.
NOTE:
The fault relay output (if
programmed) will be triggered only if "Both IP
and GSM Faults" is selected.
Press the [space] key to scroll through choices.
UL:
Must be set to "Both IP and GSM Faults".
23
Flt Rel ON Y/N
(N)_
[Y], [N]
If enabled, the fault open collector output is
normally energized to ground, and de-energizes
(open circuit) in the event of a module fault.
For conditions that trip the fault relay refer to
Module Supervision Features
in Section 1.
Set to [Y] if fail-safe mode is desired.
See
Wiring for
Module Fault Relay
in Section 2.
UL:
Must be set to "Y".
24
Pwr Loss Rpt
Y/N (Y)_
[Y], [N]
Sends a primary power loss report to the central
station within 1-3 hours after its detection. A
restore report is sent within 1-3 hours after
power is restored.
UL Standard Installations
(using
transformer and battery)
:
Must be set to "Y".
25
Low Bat Rpt Y/N
(Y)_
[Y], [N]
Sends a low-battery report when a low battery
condition exists. A low-battery restore is
automatically sent when the low battery
condition clears.
UL Standard Installations
(using
transformer and battery)
:
Must be set to "Y".
26
Tamper Rpt Y/N
(Y)_
[Y], [N]
Sends a tamper report when the module detects
a tamper condition. A tamper restore is
automatically sent when the tamper condition
clears.
UL:
Must be set to "Y".
Содержание AlarmNet IGSMHS
Страница 2: ......
Страница 10: ...IGSMHS Installation and Setup Guide 1 6 ...
Страница 18: ......
Страница 40: ...IGSMHS Installation and Setup Guide 3 22 ...
Страница 44: ...IGSMHS Installation and Setup Guide 4 4 ...
Страница 52: ...IGSMHS Installation and Setup Guide A 2 ...
Страница 54: ...IGSMHS Installation and Setup Guide B 2 ...
Страница 58: ...IGSMHS Installation and Setup Guide D 2 ...
Страница 59: ...NOTES ...
Страница 60: ...NOTES ...
Страница 61: ...NOTES ...
Страница 62: ...NOTES ...