IGSMHS Installation and Setup Guide
3-8
PROMPTS
ENTRY
OPTIONS
DESCRIPTION
37
Zn7 Trigger Type
(V)_
(V+)
(V–)
(EOLR)
Selects the triggering method for this zone input.
Press the [space] key to scroll choices.
UL:
V+ must be set as inverted and V– as
non-inverted.
38
Invert Zn7 Y/N
(N)_
[Y], [N]
Inverts the alarm and normal states of the zone 7
trigger; otherwise, uses normal input signal.
39
Restore Zn7 Y/N
(Y)_
[Y], [N]
Enables restore reporting for zone 7.
40
Delay Zn7 (secs)
(00)_
[01-15]
[00] = no delay
Defines the reporting delay in seconds for zone 7.
UL:
Must be set to 00.
NOTE:
Prompts 41 through 46 only appear if the Comm Path Choice is IP, or IP&GSM.
41
Use DHCP Y/N
(Y)_
[Y], [N]
Dynamically allocates the IP addresses (recom-
mended); then skip to Prompt 46: "Enable Pwr Save".
If [N], uses fixed IP addresses.
42
NIC IP Address:
255.255.255.255_
12 digit:
xxx.xxx.xxx.xxx
Enter the 4-part address for this device. The 4 parts
of the address must be separated by spaces (displayed
as periods in Review mode).
43
Subnet Mask:
255.255.255.255_
12 digit:
xxx.xxx.xxx.xxx
Enter the 32-bit address mask used to indicate the
portion (bits) of the IP address that is being used for
the subnet address. The 4 parts of the address must
be separated by spaces (displayed as periods in
Review mode).
44
Gateway IP Addr:
255.255.255.255_
12 digit:
xxx.xxx.xxx.xxx
Enter the 4-part address assigned to the Gateway.
The 4 parts of the address must be separated by
spaces (displayed as periods in Review mode).
45
DNS Serv IP Addr:
255.255.255.255_
12 digit:
xxx.xxx.xxx.xxx
Enter the 4-part IP address assigned to the DNS
(Domain Name System) server. The 4 parts of the
address must be separated by spaces (displayed as
periods in Review mode).
46
Enable Pwr Save
(Y)_
[Y], [N]
To meet the 24 hour UL battery backup requirement,
choose "Y" to enable this feature. If this causes
connectivity problems with certain routers or
switches, then choose "N" and wire the
communications module so it is plugged into a UL
listed UPS.
UL:
Must be set to Y.
47
IP Connection
(Present)
Present
Auto Detect
Press the [space] key to toggle between the options.
Press [ENTER] to select the configuration.
If “Present” is chosen, it is assumed that an IP is
connected to the device. If it is not detected, a Pri-
mary Comm Path Failure message will be delivered
after the programmed fault time expires.
If “Auto Detect” is chosen, the device will always try to
use IP to communicate but it will not generate a
Primary Comm Path Failure unless it previously
detected the presence of IP. As soon as the presence of
IP is detected, a Primary Comm Path Restore message
is generated and the value of IP Connectivity pro-
gramming parameter is changed from “Auto Detect” to
“Detected”.
From this point on, the software expects connectivity.
The auto detect logic will resume only when the
parameter is changed back to “Auto Detect”.
Содержание AlarmNet IGSMHS
Страница 2: ......
Страница 10: ...IGSMHS Installation and Setup Guide 1 6 ...
Страница 18: ......
Страница 40: ...IGSMHS Installation and Setup Guide 3 22 ...
Страница 44: ...IGSMHS Installation and Setup Guide 4 4 ...
Страница 52: ...IGSMHS Installation and Setup Guide A 2 ...
Страница 54: ...IGSMHS Installation and Setup Guide B 2 ...
Страница 58: ...IGSMHS Installation and Setup Guide D 2 ...
Страница 59: ...NOTES ...
Страница 60: ...NOTES ...
Страница 61: ...NOTES ...
Страница 62: ...NOTES ...