Function:
A first-order digital low pass filter time constant for
suppressing electrical noise in terminal 54. A high time constant value
improves dampening, but also increases time delay through the filter.
●
ATTENTION!
This parameter cannot be changed while motor runs.
C06.26 Terminal AIN Filter Time Constant Default setting 0.01s
Range
[0.01 - 10.00 s] Enter time constant.
C06.8* LCP Potmeter
The LCP potmeter can be selected either as Reference Resource or
Relative Reference Resource.
ATTENTION!
In Hand mode the LCP potmeter functions as local
reference.
●
Function:
The scaling value corresponding to 0.
Enter low reference value. The reference value corresponding to
potentiometer turned fully counterclockwise (0 degrees).
C06.81 LCP potm. Low Ref./Feedb. Value Default setting 0.000
Range
[-4999.000 -4999.000]
●
Function:
The scaling value corresponding to the maximum reference
feedback value set in par. C03.03.
Enter high reference value. The reference value corresponding to
potentiometer turned fully clockwise (200 degrees).
C06.82 LCP potm. High Ref./Feedb. Value
Default setting 50.000
Range
[-4999.000 -4999.000]
C06.9* Analog Output
These parameters are for configuring the analog outputs of the frequency
converter.
C06.90 Terminal AON Mode
Default setting
0
Range
[0] 0 - 20 mA Range for analog outputs is 0-20
mA
[1] 4-20 mA Range for analog outputs is 4 - 20
mA
[2] Digital Functions as slow reacting digital
output. Set value to either 0
mA (off) or 20 mA (on), see par.
C06.92.