HLP-NV Series
HLP-NV Series
-
58
-
C03.5* Ramp2
See par. C03.4* for a description of ramp types.
ATTENTION!
Ramp2 - alternative ramp times: Changing from Ramp1
to Ramp2 is done via the digital input. See par. C05.1*, selection[34].
C03.50 Ramp 2 Type
Default setting
0
Range
[0] Linear
Constant acceleration/deceleration.
[2] S-ramp S m o o t h j e r k c o m p e n s a t e d
acceleration/deceleration.
●
Function:
Enter ramp-up time from 0 Hz to rated motor speed (nM,N)
set in par. C01.25.
Choose a ramp-up time ensuring that output current does not exceed
current limit set in par. C04.18 during ramping.
* only for NV4,NV5
C03.51 Ramp 2 Ramp up Time
Default setting 3.00/
15.00S*
Range
[0.05 - 3600 s]
●
Function:
Enter ramp down time from rated motor speed nM,N in par.
C01.25 to 0 Hz.
Choose a ramp down time that does not cause over-voltage in inverter
due to regenerative operation of motor. Furthermore, generated current
must not exceed current limit set in par. C04.18.
* only for NV4,NV5
C03.52 Ramp 2 Ramp down Time
Default setting 3.00/
30
.
00S*
Range
[0.05 - 3600 s]
C03.8* Other Ramps
This section contains parameters for Jog and Quick Stop Ramp
With a Jog Ramp you can both ramp up and down whereas you can only
ramp down with the Quick Stop Ramp.
●
Function:
A linear ramp applicable when Jog is activated. See par.
C05.1*, selection [14].
Ramp up time = Ramp down time.
Jog Ramp time starts upon activation of a jog signal via a selected
digital input or serial communication port.
* only for NV4,NV5
C03.80 Jog Ramp Time
Default setting 3.00/
15.00S*
Range
[0.05 - 3600 s]