HLP-NV Series
HLP-NV Series
-
11
-
IV. Storage and Installation
1. Storage
The inverter must be kept in its original package box before installation.
Pay attention to the followings when keeping it in storage if the inverter
is not used for the time being:
● It must be stored in a dry place without rubbish or dust.
● The suitable temperature for storage is between -20
℃
and +65
℃
.
● The relative humidity required is 0-95% without condensation.
● There is no corrosive gas or liquid in the storage ambience.
● It’s better to lay the inverter on a rack and keep it in a proper package.
● It is better not to store the inverter for long time. Long time storage of
the inverter will lead to the deterioration of electrolytic capacity. If it
needs to be stored for a long time make sure to power it up one time
within a year and the power-up time should be at least above five hours.
When powered up the voltage must be increased slowly with a voltage
regulator to the rated voltage value.
2. Installation Site and Environment
The inverter should be installed at the following location:
● Ambient temperature -5
℃
to 40
℃
with good ventilation.
● No water drop and low moisture.
● Free from direct sunshine, high temperature and heavy dust fall.
● Free from corrosive gas or liquid.
● Less dust, oil gas and metallic particles
● Free from vibration and easy for service and inspection.
● Free from the interference of electromagnetic noise.
Attention: The ambient conditions of the inverter will affect its
service life.
3. Installation and Direction
● There must be enough space left around the inverter for easy
maintenance and cooling.
● The inverter must be installed vertically with the smooth ventilation