HLP-NV Series
HLP-NV Series
-
99
-
Appendix 4. Simple Example of Appliaction
1
:
Parameter Initialization
C14.22 used to reset parameter to default settings
• Set C14.22 = 2
• Hold down“ENTER”to confirm changing
• Cut off mains
• Resart the drive
。
E80 was displayed to indicate the completion of the process
• Press“Off/Reset”key to confirm the operation
。
2
:
Use LCP to control the drive
1. Press “Hand” key
2. Reference source: Potentiometer or arrow keys
(for LCP without pot.).
3
:
Use extern terminals to control the drive
1
.
Press AUTO key
(
Digital control and communication control are
active only in Auto mode
)
2.Connect RUN with EV to operate the drive(terminal RUN was set to
“RUN”function )
3
.
Analogue input VI
、
AI or the pot. On LCP can be used to set
reference.
4
:
AMT sequence (Automatic motor tuning)
1. Stop the drive and make sure motor is at standstill
2. Enter motor nameplate data to C01.20 to C01.25 .
3. choose [2] of C01.29 to enable AMT.
4. Apply start signal: press “Hand”via LCP or Apply start signal in
Auto mode, - AT – will be displayed
5. AMT completed till “PUSH ENT” was displyed
Note: AMT dose not need to rotate motor.
5:Speed UP/ Down(UP DOWN)