[0] No Operation
Default for all digital and relay
outputs.
[1] Control Ready
Control board receives supply voltage.
[2] Drive Ready
Frequency converter is ready for
operation and applies supply signal on
control board.
[3] Drive Ready, Remote
Frequency converter is ready for
operation in Auto On-mode.
[4] Enable/No Warning
Frequency converter is ready for
operation. No start or stop command
is given.
No warnings are present.
[5] Drive Running
Motor is running.
[6] Running/No Warning
Motor r uns, and no war ning are
present.
[7] Run in Range/No Warning
Motor r u ns within prog ram med
current ranges, see parameters C04.50
and C04.51. No warnings are present.
[8] Run on ref/No Warning
Motor runs at reference speed.
[9] Alarm An alarm activates output.
[10] Alarm on Warning
An alarm or warning activates output.
[12] Out of Current
Range Motor current is outside range
set in parameters C04.50 and C04.51.
[13] Below Current, low
Motor current is lower than set in par.
C04.50.
[14] Above Current, high
Motor current is higher than set in par.
C04.51.
[21] Thermal Warning
Thermal warning is present when
temperature exceeds limit in motor,
frequency converter, brake resistor or
thermistor.
[22] Ready, No Thermal Warning
Frequency converter is ready for
operation and no over-temperature
warning is present.
[23] Remote Ready, No Thermal Warning
Frequency converter is ready for
operation in Auto mode, and no over-
temperature warning is present.
[24] Ready, Voltage OK
Frequency converter is ready for
operation and mains voltage is within