HLP-NV Series
HLP-NV Series
-
82
-
●
Function:
Select reset function after tripping. Once reset, frequency
converter can be restarted.
●
warning:
Motor may start without warning.
C14.21 Automatic Restart Time
Default setting
10S
Range
[0 - 600 s]
●
Function:
Enter time interval from trip to start of automatic reset
function.
This parameter is active when par. 14-20, Reset Mode, is set to
Automatic Reset [0] - [13].
C14.22 Operation Mode
Default setting
0
Range
[0] Normal Operation
Frequency converter runs normal
operation.
[2] Initialization
Resets all parameters to default
settings, except for C15.03, C15.04
and C15.05. Frequency converter
resets during next power-up.
Par. 14-22 also reverts to default
setting Normal Operation [0].
●
Function:
Use this parameter for specifying normal operation or to
initialize all parameters, except par. C15.03, C15.04 and C15.05.
C14.26 Action At Inverter Fault
Default setting
0
Range
[0] Trip
[1] Warning
●
Function:
Enter the minimum allowable magnetization for AEO.
Selecting a low value reduces energy loss in the motor, but may also
reduce resistance to sudden load changes.
C14.41 AEO Minimum Magnetisation Default setting
66%
Range
[40 - 75%]