Specifications of Non Fuse Breaker and Wire
● When the wiring between the inverter and the motor exceeds 15
meters (shielded wire) or 50 meters (No shielded wire), much higher
dV/dT will be produced inside the coil of the motor, which will cause
the destruction to the interlay or insulation of the motor. Please use a
dedicated AC motor for the inverter or add a reactor at the inverter.
● Please lower the carrier frequency when there is a longer distance
between the inverter and the motor. Because the higher the carrier
frequency is the bigger the leakage current of high-order harmonics in
the cables will be. The leakage current will have unfavorable effect on
the inverter and other equipment.
Model
NFB
(
A
)
Input wire
mm
2
Output wire
mm
2
Control wire
mm
2
HLPNV0D1821A
16
2.5
2.5
0.5
HLPNV0D3721A
16
2.5
2.5
0.5
HLPNV0D7521A
16
2.5
2.5
0.5
HLPNV01D521A
16
2.5
2.5
0.5
HLPNV02D221A
32
4
4
0.5
HLPNV0D2523A
16
2.5
2.5
0.5
HLPNV0D3723A
16
2.5
2.5
0.5
HLPNV0D7523A
16
2.5
2.5
0.5
HLPNV01D523A
32
2.5
2.5
0.5
HLPNV02D223A
32
4
4
0.5
HLPNV03D723A
32
4
4
0.5
HLPNV0D3743A
16
2.5
2.5
0.5
HLPNV0D7543A
16
2.5
2.5
0.5
HLPNV01D543A
16
2.5
2.5
0.5
HLPNV02D243A
16
2.5
2.5
0.5
HLPNV03D043A
16
2.5
2.5
0.5
HLPNV04D043A
32
4
4
0.5
HLPNV05D543A
32
4
4
0.5
HLPNV07D543A
40
6
6
0.5
HLPNV001143A
63
6
6
0.5
HLPNV001543A
100
6
6
0.5
HLPNV18D543A
100
10
10
0.5
HLPNV002243A
100
16
16
0.5
Attention: The parameters in the list are only for reference and should not
be regarded as standard.