HLP-NV Series
HLP-NV Series
-
68
-
C06.01 Live Zero Timeout Function Default setting
0
Range
[0] Off Function is disabled.
[1] Freeze output
Output frequency remains at value
it had when live zero was detected.
[2] Stop
F r e q u e n c y c o n v e r t e r r a m p s
down to 0 Hz. Remove live zero
error condition before restarting
frequency converter.
[3] Jogging
Frequency converter ramps to jog
speed, see par. C03.41.
[4] Max Speed Frequency conver ter ramps to
Motor Speed High Limit, see par.
C04.14.
[5] Stop and Trip
Frequency converter ramps down
to 0 Hz and then trips. Remove live
zero condition and activate reset
before restarting the frequency
converter.
●
Function:
Function is activated if input signal is below 50% of value
set in parameters C06.10, C06.12 or C06.22.
C06.1* Analog Input 1
Parameters for configuring scaling and limits for analog input 1 (Terminal
VIN).
ATTENTION!
Micro switch XXX in position U: Parameters C06.10 and C06.11 are
active.
Micro switch in position I: Parameters C06.12 and C06.13 are active.