HLP-NV Series
HLP-NV Series
-
64
-
[21] Speed up
Select Speed up and Speed down if
digital control of the up/down speed
is desired (motor potentiometer).
Activate this function by selecting
either Freeze reference or Freeze
output.
When Speed up is activated for less than 400 ms. the resulting
reference will be increased by 0.1%.
If Speed up is activated for more than
400 ms. the resulting reference will
ramp according to ramp 2 in par.
C03.51.
[22] Speed down
Same as Speed up [21].
[23] Setup select bit 0
Set par. C00.10 Active set-up to Multi
set-up. Logic 0 = set-up 1, Logic 1 =
Set-up 2.
[26] Precise stop inverse
Prolong the stop signal to give a
precise stop independent of scan time.
The function is available for Terminal
EMS only.
[27] Start, precise stop
As [26], but including Start.
[28] Catch up
Select Catch up/Slow down to increase
or reduce the resulting reference value
by the percentage set in par. C03.12.
[29] Slow down
Same as Catch up [28]
[32] Pulse input (only Terminal EMS)
Select Pulse input when using a
pulse sequence as either reference or
feedback. Scaling is done in par. group
C05.5*.
[34] Ramp bit 0
Logic 0 = Ramp1, see par. C03.4*.
Logic 1 = Ramp2, see par. C03.5*.
[60] Counter A(up)
Input for counter A.
[61] Counter A(down)
Input for counter A.
[62] Reset counter A
Input for reset of counter A.
[63] Counter B(up)
Input for counter B.
[64] Counter B(down)
Input for counter B.
[65] Reset counter B
Input for reset of counter B.
C05.4* Relays
Parameter group for configuring timing and output functions for relays.
C05.40 Function Relay
Default setting
9
Range
See the following table