Advanced Configuration
41 (46)
System
Configuration
File
(chip.ini)
(continued)
Parameter
Description
V
alid
range
Default
value
MBUS_SECMASKMEDIUM
Predefined
medium
ID
for
secondary
scan
Exactly
2
characters,
0-9
each
or
0xFFFF
0xFF
MBUS_SECMASKSERIAL
Mask
for
serial
number
of
meters
for
secondary
scan
Exactly
8
characters,
0-9
or
0xF
each
0xFFFFFFFF
MBUS_SECMASKVERSION
Predefined
version
number
for
secondary
scan
Exactly
2
characters,
0-9
each
or
0xFFFF
0xFF
MBUS_SELECTMASK
Disables
parts
of
secondary
address
for
exact
selection,
wildcards
are
used
instead
(set
via
bit
mask):
+1
=
Serial
number
,
+2
=
Manufacturer
,
+4
=
V
ersion,
+8
=
Medium
0
-
15,
0
MBUS_ST
OPBITS
Stop
bits
for
serial
M-Bus
communication
1,
2
1
MBUS_TIMEOUT
T
imeout
for
M-Bus
(ms)
0
-
65535
2000
MBUS_W
AKEUPENABLE
Enables
specific
wake-up
request
0,
1
0
METER_MAXALL
V
ALUECOUNT
Limits
the
total
number
of
meter
values
(0
=
no
limit)
0
-
65535
0
METER_MAXDEVICECOUNT
Limits
the
number
of
meters
(0
=
no
limit)
0
-
65535
0
METER_MAXV
ALUECOUNT
Limits
the
number
of
meter
values
per
meter
(0
=
no
limit)
0
-
65535
0
METER_ST
A
T_CONFIG
Path
for
meter
configuration
file
T
ext
(max.
40
characters)
/app/Device_Handle.
cfg
METER_TIME
Interval
for
meter
read-out
(seconds)
IMPORT
ANT
:
Short
cycle
times
and/or
many
meters
may
cause
very
high
amounts
of
data
being
generated.
10
-
4294967295
900
MODBUS_ADDRESS
Modbus
primary
address
or
unit
identifier
0
-
255
0
MODBUS_CONNECTIONTIMEOUT
Connection
timeout
(seconds)
0
-
65535
60
MODBUS_DEBUGOUT
Enables
the
debug
output
of
Modbus
data
0,
1
0
MODBUS_DISCONNECTTIMEOUT
T
imout
for
disconnection
of
an
idle
connection
(seconds)
1
-
1000
60
MODBUS_ENABLE
Enables
the
Modbus
slaves
0,
1
0
MODBUS_MAXCONNECTIONS
Maximum
count
of
simultaneous
Modbus
TCP
connections
0
-
80
5
MODBUS_NWPOR
T
Network
port
of
the
Modbus
slave
0
-
65535
502
MODBUS_SW
AP
Swap
byte
order
of
Modbus
data
0:
MSB
first
1:
LSB
first
0,
1
0
MODBUSMETER_
PROTOCOL
VERSION
Protocol
version
of
the
Modbus
meter
data:
Bit
0
=
2
registers
per
value
(float-only)
Bit
1
=
Multislave
Bit
2
=
Word-Swa
pping
of
32-bit
values
Bit
3
=
Dummy-mode
0
-
16
0
MUC_CONFIG_VER
V
ersion
of
the
configuration
file
1,
2
2
(explicit)
M-Bus to Modbus-TCP Gateway User Manual
SCM-1202-0096-EN 2.1