Advanced Configuration
40 (46)
System
Configuration
File
(chip.ini)
Parameter
Description
V
alid
range
Default
value
[IP]
ADDRESS
IP
address
of
device
0.0.0.0
-
255.255.255.255
Not
set
NETMASK
Subnet
mask
of
device
0.0.0.0
-
255.255.255.255
Not
set
GA
TEW
A
Y
IP
address
of
device
0.0.0.0
-
255.255.255.255
Not
set
DHCP
Enabling
DHCP
look-up
0,
1
1
TCPIPMEM
Memory
for
the
webserver
(kB)
60–1000
280
[DEVICE]
NAME
Name
of
device
shown
in
Net
discover
T
ext
(max.
20
characters)
Anybus
M-Bus/MTCP
20
(80)
[CONFIG]
MBUS_BAUDRA
TE
Baud
rate
for
serial
M-Bus
communication
2400
MBUS_DA
T
ABITS
Data
bits
for
serial
M-Bus
communication
7,
8
8
MBUS_DEBUGOUT
Enables
output
of
raw
data
to
STDOUT
0,
1
0
MBUS_ENABLE
Enables
the
M-Bus
interface
0,
1
1
MBUS_FREEZESTORAGENUM
Storage
number
for
meter
data
on
Freeze
command
0
-
4294967295
0
MBUS_FULL
TIMEOUT
Maximum
timeout
for
reading
a
meter
(ms)
0-65535
10000
MBUS_IDLETIMEOUT
Idle
timeout
for
detecting
end
of
communication
0-65535
100
MBUS_MAXMUL
TIP
AGE
Limits
number
of
pages
for
multipage
request
0
-
255
10
MBUS_MAXPRIMARY
ADDRESS
Upper
limit
of
address
range
for
M-Bus
primary
scan
0
-
250
250
MBUS_MAXRETRY
Number
of
retries
for
a
M-Bus
or
multipage
request
0
-
255
3
MBUS_MINPRIMARY
ADDRESS
Lower
limit
of
address
range
for
M-Bus
primary
scan
0
-
250
0
MBUS_P
ARITY
M-Bus
parity:
0
=
no,
1
=
odd,
2
=
even,
3
=
mark,
4
=
space
0
-
4
2
MBUS_RA
WLOGENABLE
Enables
raw
data
log
to
drive
B:
0,
1
0
MBUS_REQUESTMODE
Defines
request
sequence
for
readout
DEF
AUL
T
,EXT
,ONL
Y
,FREEZE
DEF
AUL
T
MBUS_RESETDISABLE
Disables
reset
command
0,
1
0
MBUS_RESETMODE
Reset
mode:
0
=
Reset
after
select,
1
=
Reset
prior
to
select,
2
=
No
reset
0
-
2
0
MBUS_SCANMODE
Scan
mode
for
M-Bus
PRIMARYSCAN
,
SECONDARYSCAN
,
SECONDARYSCAN
ALLOC,
SECONDARYSCAN
REVERSE,
SECONDARYSCAN
ALLOCRE-
VERSE
SECONDARYSCAN
MBUS_
SECMASKMANUF
ACTURER
Predefined
manufacturer
ID
for
secondary
scan
Exactly
4
characters,
0-9
each
or
0xFFFF
0xFFFF
M-Bus to Modbus-TCP Gateway User Manual
SCM-1202-0096-EN 2.1