Advanced Configuration
43 (46)
Meter Configuration File
Parent
Element name
Description
Default value
Example
root
version
Version of XML specification
-
0x08
meter
Parent element for each meter
-
-
meter
interface
Interface to meter
-
M-Bus
serial
Serial number of meter
(hexadecimal notation with leading
0x
)
0xFFFFFFFF
0x30101198
manufacturer
Manufacturer of meter (abbreviation)
Not set
SLV
version
Version of meter
Not set
0x01
medium
Medium of meter
(see
Meter Data Format, p. 26
)
Not set
Electricity
primaryaddress
Primary address of meter
(M-Bus or S0)
0
0x03
addressmode
Used mode for addressing:
0 = Secondary,1 =: Primary
0
0
readoutcycle
Specific read-out interval (seconds)
0
900
maxvaluecount
Limit for number of meter values
0
12
encryptionkey
Encryption key for meter (AES for
wM-Bus)
Not set, 0
0x82 0xB0 0x55 0x11 0x91
0xF5 0x1D 0x66 0xEF 0xCD
0xAB 0x89 0x67 0x45 0x23
0x01
active
Enables logging of meter data or
transmission via WAN interface
1
1
rssi
Received Signal Strength Indicator at last
reception (wM-Bus)
0
123
register
Allocated Modbus register
0
20
value
Parent element for meter values
-
-
value
description
Description of value
(see
Meter Data Format, p. 26
)
None
Energy
unit
Unit of value
(see
Meter Data Format, p. 26
)
None
Wh
encodetype
Coding of value
NODATA
INT32
scale
Scale factor (scientific notation)
1e0
1e-3
valuetype
Type of value: instantaneous, maximum,
minimum, errorstate
instantaneous
instantaneous
storagenum
Storage number of value
0
2
tariff
Tariff information for value
0
3
confdata
Generic data, OBIS code for value (X-X:X.
X.X*X; X=0...255)
(
OBIS-ID
in tab
Meter
)
Not set
0x01 0x00 0x01 0x08 0x00
0xFF
active
Enables logging of value data or
transmission via WAN interface
1
1
register
Allocated Modbus register
0
30
user
User specified, max. 50 chars
(
User label
in tab
Meter
)
Not set
OG-1-Re
M-Bus to Modbus-TCP Gateway User Manual