Configuration
15 (46)
Configuration tab fields
Field
Description
Writable
Readout interval (s)
Standard readout cycle of meters (in seconds). Value might be overwritten for each
meter by parameter Cycle in tab Meter
Yes
Description mode
Mode of displaying the meter value description.
None
No display of description
Standard
Display of common value description.
Extended
Extended display of value description (if not 0).
Notation: Description [Memory] <Tariff> {min|max|error}
Example:
Energy [2] <1> {max}
Extended
with DIF/VIF
Extended display including DIF and VIF raw data.
Notation: Description [Memory] <Tariff> {Value Type} # XX XX XX…
Example:
Energy [2] <1> # 8C 11 04
Extended
with raw data
Extended display including raw data of the complete value entry.
Notation: Description [Memory] <Tariff> {Value Type} # XX XX XX…
Example:
Energy [2] <1> # 8C 11 04 96 47 06 00
DIF/VIF
Display of DIF/VIF raw data
Raw data
Displays the raw data of the complete meter value entry.
After changing this parameter a readout is needed to update the
meter list and to display the relevant data.
Yes
Maximum device count
Maximum number of meters to scan (0 = no limitation).
Already configured meters are not affected by this parameter.
Yes
Maximum value count
Maximum number of meter value entries to read during a readout (0 = no limitation).
Already configured meter value entries are not affected by this parameter.
Yes
RAW log active
Activates the raw data log.
Yes
M-Bus mode
M-Bus scan mode (secondary, reverse secondary or primary search)
Yes
Primary start address
First address for primary search
Yes
Primary final address
Last address for primary search
Yes
Secondary address
mask
Search mask for secondary search, 8 numerical characters.
F
defines a wildcard. Missing characters will be filled up with leading zeros
Yes
M-Bus baud rate
Baudrate for M-Bus communication (300–19200 baud)
Yes
M-Bus timeout
M-Bus timeout until reception of first data (ms)
Yes
M-Bus idle timeout
M-Bus timeout until end of reception (ms)
Yes
M-Bus full timeout
M-Bus timeout (complete) for reception of a whole data packet (ms)
Yes
M-Bus request mode
Mode of the M-Bus readout (REQ_UD2)
Standard
Readout with REQ_UD2
Extended 1
Readout with Get-All-Data (DIF/VIF 7F 7E) and REQ_UD2
Extended 2
Readout with Get-All-Data (DIF 7F) and REQ_UD2
Yes
M-Bus reset mode
Mode of the M-Bus Reset (before scan and readout)
None
No reset
Standard
Send SND_NKE to primary address of the meter or broadcast
address when using secondary adressing.
Extended 1
Send SND_NKE to primary address FD and SND_NKE to primary
address of the meter or broadcast address when using secondary
addressing.
Extended 2
Send SND_NKE and an Application Reset to primary address FD
and a SND_NKE to the primary address of the meter or to
broadcast address when using secondary addressing.
Yes
M-Bus max. multipage
Limits the count of multipage requests
Yes
M-Bus to Modbus-TCP Gateway User Manual