8 Troubleshooting
197
SMGB0064 rev.0 - 08/2011
8
8.1.2 Failure of the power supply to the indoor unit and the remote control switch
•
The LED and the LCD are not indicated.
•
Not operated
If the fuses are blown out or a breaker is activated, investigate the cause of the overcurrent and take the necessary action.
Phenomenon
Cause
Check item
Action
(Turn OFF the main switch)
Power failure or power is not ON
Measure the voltage by means of
the voltmeter
Supply the power
Blown out fuse or activation of the
breaker at the power source
Short circuit supplied between the
wires
Check for any uncovered part of
the wires
Remove the cause of the short
circuit and replace the fuse
Short circuit of the wires to earth
Measure the insulation resistance
Remove the cause of the short
circuit and replace the fuse
Failure of indoor unit fan motor
Measure resistance between
wires and insulation resistance
Replace the fan motor and fuse
Blown out fuse at the control cir-
cuit
Short circuit supplied between the
wires
Check for any uncovered part of
the wires
Remove the cause of the short
circuit and replace the fuse
Short circuit of the control circuit
to earth
Measure the insulation resistance
Remove the cause of the short
circuit and replace the fuse
Failure of indoor unit fan motor
Measure the insulation resistance
Remove the cause of the short
circuit and replace the fuse
Failure of the transformer at the indoor unit side
Measure the voltage at the sec-
ondary side
Replace the transformer
Disconnected cable of the remote control switch
Connect the cable
Replace the cable or repair the
cable
Insufficient contacting at the con-
nectors of the remote control
switch
Insufficient connection or incorrect
connection of the indoor unit PCB
Check the connectors
Correctly connect the connector
Insufficient connection or incorrect
connection of the indoor unit PCB
in the remote control switch
Failure of the remote control switch
Check the remote control switch
by means of the self-check mode
*1)
Replace the remote control switch
if it failed
Failure of PCB
Unconnected wires to PCB
Check the connectors
Correctly connect the wires
Failure of PCB
Check PCB by means of the self-
check mode *2)
Replace PCB if it failed
Incorrect wiring connection
Take action according to the procedure that is displayed in “TEST RUN”
N O T E
•
*1): Refer to section
Self-checking of the remote control switch
, see on page 301
.
•
*2): Refer to section
Self-checking procedure of PCB by means of the Remote Control Switch
, see on page 299
.
Содержание RAS-(2-3)HVRN(S)(2)
Страница 2: ......
Страница 4: ...IV SMGB0064 rev 0 08 2011 Index ...
Страница 10: ...x Contens SMGB0064 rev 0 08 2011 ...
Страница 58: ...2 Unit Installation 48 SMGB0064 rev 0 08 2011 ...
Страница 119: ...4 Electrical Wiring 109 SMGB0064 rev 0 08 2011 4 RAS 4 6 HVRNM2E ...
Страница 120: ...4 Electrical Wiring 110 SMGB0064 rev 0 08 2011 RAS 4 6 HRNM2E ...
Страница 122: ...4 Electrical Wiring 112 SMGB0064 rev 0 08 2011 4 6 2 Electrical wiring diagrams for ES Series RAS 2 2 5 HVRN2 ...
Страница 123: ...4 Electrical Wiring 113 SMGB0064 rev 0 08 2011 4 RAS 3HVRNS2 ...
Страница 124: ...4 Electrical Wiring 114 SMGB0064 rev 0 08 2011 RAS 4 6 HVRNS2E ...
Страница 125: ...4 Electrical Wiring 115 SMGB0064 rev 0 08 2011 4 RAS 4 6 HRNS2E ...
Страница 126: ...4 Electrical Wiring 116 SMGB0064 rev 0 08 2011 RAS 8 10 HRNSE ...
Страница 147: ...5 Control System 137 SMGB0064 rev 0 08 2011 5 Dry operation Continues in the next page ...
Страница 149: ...5 Control System 139 SMGB0064 rev 0 08 2011 5 Heating operation Continues in the next page ...
Страница 150: ...5 Control System 140 SMGB0064 rev 0 08 2011 ...
Страница 155: ...5 Control System 145 SMGB0064 rev 0 08 2011 5 Activation for protection device control ...
Страница 164: ...5 Control System 154 SMGB0064 rev 0 08 2011 Activation for protection device control ...
Страница 168: ...5 Control System 158 SMGB0064 rev 0 08 2011 Preheating control of compressor ...
Страница 170: ......
Страница 182: ......
Страница 226: ...8 Troubleshooting 216 SMGB0064 rev 0 08 2011 ...
Страница 265: ...8 Troubleshooting 255 SMGB0064 rev 0 08 2011 8 RAS 4 6 H V RNS2E ...
Страница 266: ...8 Troubleshooting 256 SMGB0064 rev 0 08 2011 RAS 8 10 HRNSE ...
Страница 271: ...8 Troubleshooting 261 SMGB0064 rev 0 08 2011 8 RAS 8 10 HRNSE ...
Страница 294: ...8 Troubleshooting 284 SMGB0064 rev 0 08 2011 ...
Страница 298: ...8 Troubleshooting 288 SMGB0064 rev 0 08 2011 ...
Страница 336: ...9 Spare Parts 326 SMGB0064 rev 0 08 2011 9 1 Spare parts for IVX Series RAS 3HVRNM2E Cycle and structural parts ...
Страница 339: ...9 Spare Parts 329 SMGB0064 rev 0 08 2011 9 RAS 4 6 HVRNM2E Cycle and structural parts ...
Страница 342: ...9 Spare Parts 332 SMGB0064 rev 0 08 2011 RAS 4 6 HRNM2E Cycle and structural parts ...
Страница 344: ...9 Spare Parts 334 SMGB0064 rev 0 08 2011 Electrical parts ...
Страница 355: ...9 Spare Parts 345 SMGB0064 rev 0 08 2011 9 RAS 4 6 HVRNS2E Cycle structural ...
Страница 357: ...9 Spare Parts 347 SMGB0064 rev 0 08 2011 9 Electrical parts ...
Страница 359: ...9 Spare Parts 349 SMGB0064 rev 0 08 2011 9 RAS 4 6 HRNS2E Cycle structural ...
Страница 361: ...9 Spare Parts 351 SMGB0064 rev 0 08 2011 9 Electrical parts ...
Страница 363: ...9 Spare Parts 353 SMGB0064 rev 0 08 2011 9 RAS 8 10 HRNSE Cycle and structural ...
Страница 366: ...9 Spare Parts 356 SMGB0064 rev 0 08 2011 Electrical parts ...
Страница 368: ......
Страница 448: ......
Страница 470: ......
Страница 487: ......