8 Troubleshooting
321
SMGB0064 rev.0 - 08/2011
8
•
Checking procedure for the electronic expansion valve
Valve position
Electronic expansion valve
Outdoor unit electronic expansion valve
Locked fully closed
Check the temperature of the piping in the heat-
ing process. Failure of the temperature to rise
indicates a fault.
It is abnormal if the liquid pipe pressure does
not increase during the cooling process.
Locked slightly open
The following conditions indicate a fault:
-
Where the freeze protection thermistor tempe-
rature is lower than the intake air temperature.
-
Where the unit being inspected stops and
other units continue operating in cooling mode.
Electronic expansion valve
Freeze protection thermistor
It is abnormal if the liquid pipe pressure does
not increase and the outlet temperature of the
expansion valve decreases after the cooling
process starts.
Locked fully open
It is abnormal under the following conditions:
after the heating process for more than 30
minutes, the discharge gas temperature of
the compressor is not 10°C higher than the
condensing temperature and there is no other
faults, such as an excessive charge of refriger-
ant and others.}
•
Fault diagnosis of DC fan motor
About fan motor fault diagnosis.
When ISPM/DIP-IPM is faulty and Alarm 53 appears, the fan motor may also be damaged. To prevent ISPM/DIP-IPM
damage which may result from operation combined with a faulty fan motor, check also if the fan motor is not damaged
when ISPM/DIP-IPM is replaced.
C A U T I O N
-
For the shake of safety, turn OFF the power before start working.
-
Working/checking with the power ON may disturb correct diagnosis and may result in failure.
Models for ES:
DC motor(s) included in different models:
Model
Pieces
RAS-(2/2.5)HVRN2
1
RAS-3HVRNS2
1
RAS-(4-6)H(V)RNS2E
1
RAS-(8/10)HRNSE
1
Fault diagnosis procedure
1.
Remove fan motor connectors from the control PCB ISPM or DIP-IPM and turn the fan motor shaft by hand.
Normal:
Fan motor shaft turns smoothly.
Faulty:
No continuous rotary torque movement felt when turning the motor by hand. This occurs because the internal
magnet of the fan motor breaks the movement when the internal electronic circuit of the fan motor has a short-
circuit fault
2.
Measure the fan motor resistance using a tester.
Measurement procedure:
1.
Remove the fan motor connector from the control PCB, ISPM or DIP-IPM.
2.
Connect the black test lead of the tester to the black wire pin of the fan motor connector
3.
Connect the red test lead to the wire connector pin to be checked
Results
Normal:
Observed values will be close to the normal values in the table below
Faulty:
Observed values will be deviated from the normal values in the table below.
Generally an open-circuit fault shows ∞, and a short-circuit fault shows several Ω-kΩ.)
Internal electronic circuit fault of the fan motor including short-circuit and breakage can be checked
Содержание RAS-(2-3)HVRN(S)(2)
Страница 2: ......
Страница 4: ...IV SMGB0064 rev 0 08 2011 Index ...
Страница 10: ...x Contens SMGB0064 rev 0 08 2011 ...
Страница 58: ...2 Unit Installation 48 SMGB0064 rev 0 08 2011 ...
Страница 119: ...4 Electrical Wiring 109 SMGB0064 rev 0 08 2011 4 RAS 4 6 HVRNM2E ...
Страница 120: ...4 Electrical Wiring 110 SMGB0064 rev 0 08 2011 RAS 4 6 HRNM2E ...
Страница 122: ...4 Electrical Wiring 112 SMGB0064 rev 0 08 2011 4 6 2 Electrical wiring diagrams for ES Series RAS 2 2 5 HVRN2 ...
Страница 123: ...4 Electrical Wiring 113 SMGB0064 rev 0 08 2011 4 RAS 3HVRNS2 ...
Страница 124: ...4 Electrical Wiring 114 SMGB0064 rev 0 08 2011 RAS 4 6 HVRNS2E ...
Страница 125: ...4 Electrical Wiring 115 SMGB0064 rev 0 08 2011 4 RAS 4 6 HRNS2E ...
Страница 126: ...4 Electrical Wiring 116 SMGB0064 rev 0 08 2011 RAS 8 10 HRNSE ...
Страница 147: ...5 Control System 137 SMGB0064 rev 0 08 2011 5 Dry operation Continues in the next page ...
Страница 149: ...5 Control System 139 SMGB0064 rev 0 08 2011 5 Heating operation Continues in the next page ...
Страница 150: ...5 Control System 140 SMGB0064 rev 0 08 2011 ...
Страница 155: ...5 Control System 145 SMGB0064 rev 0 08 2011 5 Activation for protection device control ...
Страница 164: ...5 Control System 154 SMGB0064 rev 0 08 2011 Activation for protection device control ...
Страница 168: ...5 Control System 158 SMGB0064 rev 0 08 2011 Preheating control of compressor ...
Страница 170: ......
Страница 182: ......
Страница 226: ...8 Troubleshooting 216 SMGB0064 rev 0 08 2011 ...
Страница 265: ...8 Troubleshooting 255 SMGB0064 rev 0 08 2011 8 RAS 4 6 H V RNS2E ...
Страница 266: ...8 Troubleshooting 256 SMGB0064 rev 0 08 2011 RAS 8 10 HRNSE ...
Страница 271: ...8 Troubleshooting 261 SMGB0064 rev 0 08 2011 8 RAS 8 10 HRNSE ...
Страница 294: ...8 Troubleshooting 284 SMGB0064 rev 0 08 2011 ...
Страница 298: ...8 Troubleshooting 288 SMGB0064 rev 0 08 2011 ...
Страница 336: ...9 Spare Parts 326 SMGB0064 rev 0 08 2011 9 1 Spare parts for IVX Series RAS 3HVRNM2E Cycle and structural parts ...
Страница 339: ...9 Spare Parts 329 SMGB0064 rev 0 08 2011 9 RAS 4 6 HVRNM2E Cycle and structural parts ...
Страница 342: ...9 Spare Parts 332 SMGB0064 rev 0 08 2011 RAS 4 6 HRNM2E Cycle and structural parts ...
Страница 344: ...9 Spare Parts 334 SMGB0064 rev 0 08 2011 Electrical parts ...
Страница 355: ...9 Spare Parts 345 SMGB0064 rev 0 08 2011 9 RAS 4 6 HVRNS2E Cycle structural ...
Страница 357: ...9 Spare Parts 347 SMGB0064 rev 0 08 2011 9 Electrical parts ...
Страница 359: ...9 Spare Parts 349 SMGB0064 rev 0 08 2011 9 RAS 4 6 HRNS2E Cycle structural ...
Страница 361: ...9 Spare Parts 351 SMGB0064 rev 0 08 2011 9 Electrical parts ...
Страница 363: ...9 Spare Parts 353 SMGB0064 rev 0 08 2011 9 RAS 8 10 HRNSE Cycle and structural ...
Страница 366: ...9 Spare Parts 356 SMGB0064 rev 0 08 2011 Electrical parts ...
Страница 368: ......
Страница 448: ......
Страница 470: ......
Страница 487: ......