6 Optional functions
166
SMGB0064 rev.0 - 08/2011
code “d1” “20” will be displayed if an attempt is made to change the operation mode of any of the indoor units with the
remote control.
Example of wiring diagram of fixing the operation mode.
Outdoor unit PCB
A
Power
supply
•
A: 3P connector cable.
•
X1: Cooling.
•
X2: Heating.
•
SS1: Fixing operation mode switch.
•
SS2: Change over switch
Demand thermo OFF (3)
This is an input function to control the maximum power that the compressor can consume. When this option is turned on,
the outdoor units are stopped completely, and the indoor units go into thermo-OFF. Alarm “10” is displayed on the remote
control. If the switch of this function is disconnected it becomes available again.
Connect the cabling and use the materials as shown in
Available ports
, see on page 162
Forced stoppage (4)
This is an input function that turns on when the switch receives a signal that causes the compressor and the fan motor of
the indoor unit to stop; alarm “10” displays on a remote-controlled when this option turns on. If the switch of this function is
disconnected it becomes available again.
Connect the cabling and use the materials as shown in
Available ports
, see on page 162
Current control demand (5/6/7)
This is an input function that turns on when it detects that the frequency of the compressor reaches 50%, 75% or 100%.
The frequency of the compressor is determined when the maximum current reaches the established limit.
Connect the cabling and use the materials as shown in
Available ports
, see on page 162
If the running current of the outdoor unit exceeds the maximum limit, the unit changes to the thermo-OFF condition. Stop-
page cause code “10” will appear. When the input terminal is opened during the demand current control, the control of the
input terminal is reset.
6.1.4 Description of optional output signals
Operation signal (01)
This optional signal is used to pick up the operation signal. It can be used to turn on or off complementary units of the air-
conditioning system,such as fans, humidifiers, etc.
Connect the cabling and use the materials as shown in
Available ports
, see on page 162
Note that the contact of auxiliary relay X3 is closed when an operation signal is issued.
Alarm signal (02)
This optional signal is used to pick up the activation of safety devices.
Содержание RAS-(2-3)HVRN(S)(2)
Страница 2: ......
Страница 4: ...IV SMGB0064 rev 0 08 2011 Index ...
Страница 10: ...x Contens SMGB0064 rev 0 08 2011 ...
Страница 58: ...2 Unit Installation 48 SMGB0064 rev 0 08 2011 ...
Страница 119: ...4 Electrical Wiring 109 SMGB0064 rev 0 08 2011 4 RAS 4 6 HVRNM2E ...
Страница 120: ...4 Electrical Wiring 110 SMGB0064 rev 0 08 2011 RAS 4 6 HRNM2E ...
Страница 122: ...4 Electrical Wiring 112 SMGB0064 rev 0 08 2011 4 6 2 Electrical wiring diagrams for ES Series RAS 2 2 5 HVRN2 ...
Страница 123: ...4 Electrical Wiring 113 SMGB0064 rev 0 08 2011 4 RAS 3HVRNS2 ...
Страница 124: ...4 Electrical Wiring 114 SMGB0064 rev 0 08 2011 RAS 4 6 HVRNS2E ...
Страница 125: ...4 Electrical Wiring 115 SMGB0064 rev 0 08 2011 4 RAS 4 6 HRNS2E ...
Страница 126: ...4 Electrical Wiring 116 SMGB0064 rev 0 08 2011 RAS 8 10 HRNSE ...
Страница 147: ...5 Control System 137 SMGB0064 rev 0 08 2011 5 Dry operation Continues in the next page ...
Страница 149: ...5 Control System 139 SMGB0064 rev 0 08 2011 5 Heating operation Continues in the next page ...
Страница 150: ...5 Control System 140 SMGB0064 rev 0 08 2011 ...
Страница 155: ...5 Control System 145 SMGB0064 rev 0 08 2011 5 Activation for protection device control ...
Страница 164: ...5 Control System 154 SMGB0064 rev 0 08 2011 Activation for protection device control ...
Страница 168: ...5 Control System 158 SMGB0064 rev 0 08 2011 Preheating control of compressor ...
Страница 170: ......
Страница 182: ......
Страница 226: ...8 Troubleshooting 216 SMGB0064 rev 0 08 2011 ...
Страница 265: ...8 Troubleshooting 255 SMGB0064 rev 0 08 2011 8 RAS 4 6 H V RNS2E ...
Страница 266: ...8 Troubleshooting 256 SMGB0064 rev 0 08 2011 RAS 8 10 HRNSE ...
Страница 271: ...8 Troubleshooting 261 SMGB0064 rev 0 08 2011 8 RAS 8 10 HRNSE ...
Страница 294: ...8 Troubleshooting 284 SMGB0064 rev 0 08 2011 ...
Страница 298: ...8 Troubleshooting 288 SMGB0064 rev 0 08 2011 ...
Страница 336: ...9 Spare Parts 326 SMGB0064 rev 0 08 2011 9 1 Spare parts for IVX Series RAS 3HVRNM2E Cycle and structural parts ...
Страница 339: ...9 Spare Parts 329 SMGB0064 rev 0 08 2011 9 RAS 4 6 HVRNM2E Cycle and structural parts ...
Страница 342: ...9 Spare Parts 332 SMGB0064 rev 0 08 2011 RAS 4 6 HRNM2E Cycle and structural parts ...
Страница 344: ...9 Spare Parts 334 SMGB0064 rev 0 08 2011 Electrical parts ...
Страница 355: ...9 Spare Parts 345 SMGB0064 rev 0 08 2011 9 RAS 4 6 HVRNS2E Cycle structural ...
Страница 357: ...9 Spare Parts 347 SMGB0064 rev 0 08 2011 9 Electrical parts ...
Страница 359: ...9 Spare Parts 349 SMGB0064 rev 0 08 2011 9 RAS 4 6 HRNS2E Cycle structural ...
Страница 361: ...9 Spare Parts 351 SMGB0064 rev 0 08 2011 9 Electrical parts ...
Страница 363: ...9 Spare Parts 353 SMGB0064 rev 0 08 2011 9 RAS 8 10 HRNSE Cycle and structural ...
Страница 366: ...9 Spare Parts 356 SMGB0064 rev 0 08 2011 Electrical parts ...
Страница 368: ......
Страница 448: ......
Страница 470: ......
Страница 487: ......