8 Troubleshooting
278
SMGB0064 rev.0 - 08/2011
Alarm code
57
Abnormality of fan motor protection (DC fan motor) for ES Series
• The RUN LED flickers and “ALARM” is displayed on the remote control switch.
• The unit number, the alarm code and the unit code are alternately displayed on the set temperature section. The unit
number and the alarm code are displayed on the display of the outdoor unit PCB.
-
The fan motor stops when the revolution output from the fan motor is 20 rpm for RAS-(2-3)HVRN(S)2 / 10 rpm for
RAS-(4-10)H(V)RNS(2)E or lower during 30 seconds after the fan motor activation.
-
The alarm is indicated when the abnormality is repeated 4 times for RAS-(2-3)HVRN(S)2 / 10 times for RAS-(4-10)
H(V)RNS(2)E within 5 minutes after the first detection.
N O T E
•
In the case that the fan motor does not run even the PCB1 is replaced, replace PCB5.
•
Check to ensure that DC Fan Motor is checked according to the item
Procedure of checking other main parts
for ES Series
, see on page 312
Содержание RAS-(2-3)HVRN(S)(2)
Страница 2: ......
Страница 4: ...IV SMGB0064 rev 0 08 2011 Index ...
Страница 10: ...x Contens SMGB0064 rev 0 08 2011 ...
Страница 58: ...2 Unit Installation 48 SMGB0064 rev 0 08 2011 ...
Страница 119: ...4 Electrical Wiring 109 SMGB0064 rev 0 08 2011 4 RAS 4 6 HVRNM2E ...
Страница 120: ...4 Electrical Wiring 110 SMGB0064 rev 0 08 2011 RAS 4 6 HRNM2E ...
Страница 122: ...4 Electrical Wiring 112 SMGB0064 rev 0 08 2011 4 6 2 Electrical wiring diagrams for ES Series RAS 2 2 5 HVRN2 ...
Страница 123: ...4 Electrical Wiring 113 SMGB0064 rev 0 08 2011 4 RAS 3HVRNS2 ...
Страница 124: ...4 Electrical Wiring 114 SMGB0064 rev 0 08 2011 RAS 4 6 HVRNS2E ...
Страница 125: ...4 Electrical Wiring 115 SMGB0064 rev 0 08 2011 4 RAS 4 6 HRNS2E ...
Страница 126: ...4 Electrical Wiring 116 SMGB0064 rev 0 08 2011 RAS 8 10 HRNSE ...
Страница 147: ...5 Control System 137 SMGB0064 rev 0 08 2011 5 Dry operation Continues in the next page ...
Страница 149: ...5 Control System 139 SMGB0064 rev 0 08 2011 5 Heating operation Continues in the next page ...
Страница 150: ...5 Control System 140 SMGB0064 rev 0 08 2011 ...
Страница 155: ...5 Control System 145 SMGB0064 rev 0 08 2011 5 Activation for protection device control ...
Страница 164: ...5 Control System 154 SMGB0064 rev 0 08 2011 Activation for protection device control ...
Страница 168: ...5 Control System 158 SMGB0064 rev 0 08 2011 Preheating control of compressor ...
Страница 170: ......
Страница 182: ......
Страница 226: ...8 Troubleshooting 216 SMGB0064 rev 0 08 2011 ...
Страница 265: ...8 Troubleshooting 255 SMGB0064 rev 0 08 2011 8 RAS 4 6 H V RNS2E ...
Страница 266: ...8 Troubleshooting 256 SMGB0064 rev 0 08 2011 RAS 8 10 HRNSE ...
Страница 271: ...8 Troubleshooting 261 SMGB0064 rev 0 08 2011 8 RAS 8 10 HRNSE ...
Страница 294: ...8 Troubleshooting 284 SMGB0064 rev 0 08 2011 ...
Страница 298: ...8 Troubleshooting 288 SMGB0064 rev 0 08 2011 ...
Страница 336: ...9 Spare Parts 326 SMGB0064 rev 0 08 2011 9 1 Spare parts for IVX Series RAS 3HVRNM2E Cycle and structural parts ...
Страница 339: ...9 Spare Parts 329 SMGB0064 rev 0 08 2011 9 RAS 4 6 HVRNM2E Cycle and structural parts ...
Страница 342: ...9 Spare Parts 332 SMGB0064 rev 0 08 2011 RAS 4 6 HRNM2E Cycle and structural parts ...
Страница 344: ...9 Spare Parts 334 SMGB0064 rev 0 08 2011 Electrical parts ...
Страница 355: ...9 Spare Parts 345 SMGB0064 rev 0 08 2011 9 RAS 4 6 HVRNS2E Cycle structural ...
Страница 357: ...9 Spare Parts 347 SMGB0064 rev 0 08 2011 9 Electrical parts ...
Страница 359: ...9 Spare Parts 349 SMGB0064 rev 0 08 2011 9 RAS 4 6 HRNS2E Cycle structural ...
Страница 361: ...9 Spare Parts 351 SMGB0064 rev 0 08 2011 9 Electrical parts ...
Страница 363: ...9 Spare Parts 353 SMGB0064 rev 0 08 2011 9 RAS 8 10 HRNSE Cycle and structural ...
Страница 366: ...9 Spare Parts 356 SMGB0064 rev 0 08 2011 Electrical parts ...
Страница 368: ......
Страница 448: ......
Страница 470: ......
Страница 487: ......