7 Test Run
193
SMGB0064 rev.0 - 08/2011
7
Check list on compressor
CLIENT:
MODEL:
DATE:
Serial No.:
Production date:
Checker:
N°
Check item
Check method
Result
Remarks
1
Is THM9 correctly connected?
THM9: Discharge gas thermistor
(1) Is wire of thermistor correctly connected by
viewing?
(2) Check to ensure the 7-segment indication of
Td when comp. is operating.
Td: Temperature of THM9
2
Is thermistor THM9 disconnected?
(1) Check to ensure that thermistor on the top
of comp. is correctly mounted by viewing?
(2) Check to ensure that actually measured
temp. is the same as the indication during
check mode.
3
Is current sensor faulty?
(1) Check to ensure that indication A1 and A2
are 0 during compressor stopping.
(2) Check to ensure that indication A1 and A2
are not 0 during compressor running.
4
Is current sensing part on PCB2
faulty?
5
Is the direction of current sensor
(CTU, CTV) reverse?
Check the direction => by viewing.
6
Are power source wires, U and
V inserted correctly into current
sensor?
Check to ensure that wires are correctly inser-
ted.
7
Is exp. valve (MV1) correctly con-
nected?
Check to ensure that MV1 to CN5A is correctly
connected.
8
Is exp. valve (MV1) coil correctly
connected?
Check to ensure that each coil is correctly
mounted on the valve.
9
Are the refrigeration cycle and
electrical wiring system incorrectly
connected?
Check to ensure that refrigerant is flowing into
indoor units by operating one refrigerating cycle
only from the outdoor unit.
10
Is opening of exp. valve completely
closed (locked)?
Check the following by the check mode of
outdoor units.
(1) Liquid pipe temp. (TL) < air intake temp.
(Ti) during cooling operation
(2) Liquid pipe temp. (TL) > air intake temp.
(Ti) during heating operation
11
Is opening of exp. valve fully ope-
ned (locked)?
Check to ensure that liquid pipe temp. is lower
than air intake temp. of stopping indoor unit
when other indoor units are operating under
cooling operation
12
Are the contacts for comp. magnetic
switch CMC1 faulty?
Check the surface of each contact (L1, L2 and
L3) by viewing.
13
Is there any voltage abnormality
among L1-L2, L2-L3 and L3- L1?
Check to ensure that voltage imbalance is sma-
ller than 3%. Please note that power source
voltage must be within 380 V or 220 V+10%.
14
Is the comp. oil acidified during
compressor motor burning?
Check to ensure that the oil color is not black.
Содержание RAS-(2-3)HVRN(S)(2)
Страница 2: ......
Страница 4: ...IV SMGB0064 rev 0 08 2011 Index ...
Страница 10: ...x Contens SMGB0064 rev 0 08 2011 ...
Страница 58: ...2 Unit Installation 48 SMGB0064 rev 0 08 2011 ...
Страница 119: ...4 Electrical Wiring 109 SMGB0064 rev 0 08 2011 4 RAS 4 6 HVRNM2E ...
Страница 120: ...4 Electrical Wiring 110 SMGB0064 rev 0 08 2011 RAS 4 6 HRNM2E ...
Страница 122: ...4 Electrical Wiring 112 SMGB0064 rev 0 08 2011 4 6 2 Electrical wiring diagrams for ES Series RAS 2 2 5 HVRN2 ...
Страница 123: ...4 Electrical Wiring 113 SMGB0064 rev 0 08 2011 4 RAS 3HVRNS2 ...
Страница 124: ...4 Electrical Wiring 114 SMGB0064 rev 0 08 2011 RAS 4 6 HVRNS2E ...
Страница 125: ...4 Electrical Wiring 115 SMGB0064 rev 0 08 2011 4 RAS 4 6 HRNS2E ...
Страница 126: ...4 Electrical Wiring 116 SMGB0064 rev 0 08 2011 RAS 8 10 HRNSE ...
Страница 147: ...5 Control System 137 SMGB0064 rev 0 08 2011 5 Dry operation Continues in the next page ...
Страница 149: ...5 Control System 139 SMGB0064 rev 0 08 2011 5 Heating operation Continues in the next page ...
Страница 150: ...5 Control System 140 SMGB0064 rev 0 08 2011 ...
Страница 155: ...5 Control System 145 SMGB0064 rev 0 08 2011 5 Activation for protection device control ...
Страница 164: ...5 Control System 154 SMGB0064 rev 0 08 2011 Activation for protection device control ...
Страница 168: ...5 Control System 158 SMGB0064 rev 0 08 2011 Preheating control of compressor ...
Страница 170: ......
Страница 182: ......
Страница 226: ...8 Troubleshooting 216 SMGB0064 rev 0 08 2011 ...
Страница 265: ...8 Troubleshooting 255 SMGB0064 rev 0 08 2011 8 RAS 4 6 H V RNS2E ...
Страница 266: ...8 Troubleshooting 256 SMGB0064 rev 0 08 2011 RAS 8 10 HRNSE ...
Страница 271: ...8 Troubleshooting 261 SMGB0064 rev 0 08 2011 8 RAS 8 10 HRNSE ...
Страница 294: ...8 Troubleshooting 284 SMGB0064 rev 0 08 2011 ...
Страница 298: ...8 Troubleshooting 288 SMGB0064 rev 0 08 2011 ...
Страница 336: ...9 Spare Parts 326 SMGB0064 rev 0 08 2011 9 1 Spare parts for IVX Series RAS 3HVRNM2E Cycle and structural parts ...
Страница 339: ...9 Spare Parts 329 SMGB0064 rev 0 08 2011 9 RAS 4 6 HVRNM2E Cycle and structural parts ...
Страница 342: ...9 Spare Parts 332 SMGB0064 rev 0 08 2011 RAS 4 6 HRNM2E Cycle and structural parts ...
Страница 344: ...9 Spare Parts 334 SMGB0064 rev 0 08 2011 Electrical parts ...
Страница 355: ...9 Spare Parts 345 SMGB0064 rev 0 08 2011 9 RAS 4 6 HVRNS2E Cycle structural ...
Страница 357: ...9 Spare Parts 347 SMGB0064 rev 0 08 2011 9 Electrical parts ...
Страница 359: ...9 Spare Parts 349 SMGB0064 rev 0 08 2011 9 RAS 4 6 HRNS2E Cycle structural ...
Страница 361: ...9 Spare Parts 351 SMGB0064 rev 0 08 2011 9 Electrical parts ...
Страница 363: ...9 Spare Parts 353 SMGB0064 rev 0 08 2011 9 RAS 8 10 HRNSE Cycle and structural ...
Страница 366: ...9 Spare Parts 356 SMGB0064 rev 0 08 2011 Electrical parts ...
Страница 368: ......
Страница 448: ......
Страница 470: ......
Страница 487: ......