Element
Optional function
Individual
setting
Settings
Setting conditions
Description
C7
Cancellation of forced
compressor operation
for at least 3 minutes
O
00
Function disabled
(factory setting)
This function is available depending
on the setting of function b3.
01
Function enabled
(Compressor operation during 3
minutes is no longer forced)
C8
Control by the
temperature sensor
of the remote control
switch
?
N O T E
The
remote
control
switch shall be installed
in a proper place for
the correct detection of
room temperature by its
temperature sensor.
O
00
Control by the air inlet sensor of
indoor units (factory setting)
This function specifies the
temperature sensor to be used as
control sensor by the indoor unit.
01
Control by the temperature sensor
of the remote control switch
02
Control by the average value of
the air inlet sensor of indoor units
and the temperature sensor of the
remote control switch.
(Air inlet + Remote control switch)/2
Control sensor when
a remote sensor is
connected to the THM4
connector in the indoor
unit PCB
?
N O T E
The
remote
sensor
shall be installed in a
proper place for the
correct detection of room
temperature.
Model
RPF(I)-FSN2E
O
00, 01, 02
When a remote sensor is connected
to THM4, this remote sensor is
used as control sensor, whichever
the setting for C8
(factory setting C8=00)
Control sensor when
a remote sensor is
connected to the THM4
connector in the indoor
unit PCB
?
N O T E
The
remote
sensor
shall be installed in a
proper place for the
correct detection of room
temperature.
Models
RCI-FSN4
RCIM-FSN4E
RCD-FSN3
RPC-FSN3
RPI-FSN5E
RPI-FSN3E(P)E(-f)
RPIM-FSN4E(-DU)
RPK-FSN(H)3M
00, 02
Air temperature control using
the average value of the air inlet
thermistor and the remote sensor
(factory setting C8=00)
(Air inlet + Remote sensor)/2
01
Air temperature control using the
remote sensor
C9
Not available
–
“- -”
permanent –
–
CA
Not available
–
“- -”
permanent –
–
Cb
Selection of forced
stoppage logic
X
00
Forced stoppage input: A contact,
normally open contact (factory
setting)
This function determines the logic
operation for the forced stoppage
contacts.
01
Forced stoppage input: B contact,
normally closed contact
CC
Not used
–
00
-
Use at 00 conditions
01
TEST RUN MENU
PMML0496 rev.1 - 12/2020