Element
Optional function
Individual
setting
Settings
Setting conditions
Description
FC
Lower limit of setting
temperature for cooling
(Minimum value of
setting temperature
allowed in cooling)
X
00
Function disabled
19 °C is the standard minimum set
point. (factory setting)
This function defines the lowest
temperature setting value for FAN/
COOL/DRY modes.
01
+1 ºC (Lower limit 20 ºC)
02
+2 ºC (Lower limit 21 ºC)
03
+3 ºC (Lower limit 22 ºC)
·
·
·
·
·
·
08
+8 ºC (Lower limit 27ºC)
09
+9 ºC (Lower limit 28 ºC)
10
+10 ºC (Lower limit 29 ºC)
Fd
Upper limit of setting
temperature for heating
(Maximum value of
setting temperature
allowed in heating)
X
00
Function disabled
30 ºC is the standard maximum set
point. (factory setting)
This function defines the highest
temperature setting value for
HEATING mode.
Models:
RPF(I)-)FSN2E
up to 20ºC (FC=10)
01
-1 ºC (Upper limit 29 ºC)
02
-2 ºC (Upper limit 28 ºC)
03
-3 ºC (Upper limit 27 ºC)
·
·
·
·
·
·
10
-10 ºC (Upper limit 20 ºC)
11
-11 ºC (Upper limit 19 ºC)
12
-12 ºC (Upper limit 18 ºC)
FE
Not used
-
00
-
Use at 00 conditions
01
02
FF
Not Used
O
00
-
Use as 00 conditions
01
H1
No indication of
maintenance alarm
–
00
Displayed
This function is used to display
or hide the maintenance alarm
indication.
01
Hidden
H2
Indication of hot start
(No Indication of
operation limitation)
X
00
Displayed
This function is used to display or
hide the automatic control indication.
Models:
RPF(I)-FSN2E
Not available, use at 00 conditions
01
Hidden
H3
Not used
–
00
-
Use at 00 conditions
01 / 02
H4
Not Used
–
00
-
Use at 00 conditions
01
-
KPI: Operation modes
for the ventilation unit
with energy recovery
O
00
Air conditioning only
(factory setting)
This function is only available for
ventilation units with energy recovery.
01
Ventilation only
02
Air condit ventilation
J1
Not used
-
00
-
Use at 00 conditions
01
TEST RUN MENU