ENGLISH
Input and Output Number Display and Connectors
Input number display
Port
Factory setting
Input/Output indication
Setting item
Indication
Setting
Input 1
CN3 1-2
Remote ON/OFF 1 (Level)
03
Input 2
CN3 2-3
Prohibiting Remote Control after Manual Stoppage
06
Output 1
CN7 1-2
Operation
01
Output 2
CN7 1-3
Alarm
02
Output 3
CN8 1-2
Thermo-ON for Heating
06
Input and Output Settings and Display Codes
Indication
Input
Output
00
Not set
Not set
01
Room Thermostat (for Cooling)
Operation
02
Room Thermostat (for Heating)
Alarm
03
Remote ON/OFF 1 (Level)
Cooling
04
Remote ON/OFF 2 (Operation)
Thermo-ON for Cooling
05
Remote ON/OFF 2 (Stoppage)
Heating
06
Forbidding Remote Control after Manual Stoppage
Thermo-ON for Heating
07
Remote Cooling / Heating Change
Total Heat Exchanger
08
Elevating Grille Input (not available for European models)
Elevating Grille Output (not available for European models)
09
Setback operation
?
N O T E
• After at least 3 minutes from the power ON, change the optional setting.
• Record the setting conditions for each input and output in the “Setting” column of the table.
6.5 ELEVATING GRILLE
This function is available only when the elevating grille is equipped with the air panel. European models are not equipped with this
function.
TEST RUN MENU
PMML0496 rev.1 - 12/2020
27