T-CONTROL
9
33
Term
Description
Unit
Outside temperature 2
Upper temperature of the heating curve (0 - 60)
°C
Here the maximum boiler output is limited depending on the outside
temperature. Therefore, according to the example, the maximum boiler
output at outdoor temperatures < 0°C at the set output at Temp. 1
(100%). At outside temperatures > 20°C the maximum boiler output is the
set output at Temp. 2 (50%). A linear interpolation takes place in
between.
-
Settings
1 2
3
4 5
Barrier time burner
cleaning
Setting the barrier times (1-4) for burner cleaning.
00:00-
23:59
Overview of work / pause in tabular form
-
Settings
1 2 3
4
5
Fuel selection
Display of the currently set fuel: Wood chips / Pellets
-
Overview of work / pause / suction in tabular form
-
Settings
1 2 3 4
5
ID correction nominal
load
Correction of the ID fan in nominal load operation with the aid of the ID
fan (observe air correction of the lambda sensor).
-75-
+75 %
ID correction part load
Correction of the ID fan in nominal load operation with the aid of the ID
fan (observe air correction of the lambda sensor).
-75-
+75 %
Mat. correction part
load
Correction of the amount of material in part load operation by using the
stoker screw (observe material correction of the lambda probe).
-95-
+95 %
Mat. correction
nominal load
Correction of the amount of material in nominal load operation by using
the stoker screw (observe material correction of the lambda probe)
-95-
+95 %
Overview of work / pause / suction in tabular form
-
menu
"inputs / outputs" (system-specific)
In-/Outputs
1
2 3 4 5 6 7
Grate cleaning
Indicates the state of the grate cleaning:
If switch on green
Output active.
-
Burning chamber- / ash
door opened
Indicates the state of the ash door.
If the indicator lamp lights up, the ash door is opened.
-
BFP flap open
Displays the condition of the BFP flap Open:
If switch on green
Output active.
-
motor protection
Discharge
Display of the status of the motor protection discharge: If the control lamp
is lit, the discharge motor protection input has triggered.
-
End switch room
discharge
Display of the status of the end switch room discharge: If the control lamp
is lit, the end switch room discharge input has triggered.
-
Содержание firematic PELLET 120
Страница 1: ...OPERATING INSTRUCTIONS Wood chips pellets heating system firematic PELLET 120 201 ...
Страница 19: ...Temperature manager 8 19 Fig 8 6 Example temperature manager when time mode without difference ...
Страница 84: ...15 Annex 84 15 ANNEX 15 1 Additional boiler module Hydraulic recommendation 1 ...
Страница 85: ...Annex 15 85 Hydraulic recommendation 2 ...
Страница 86: ...15 Annex 86 15 2 Solar module Program 1 ...
Страница 87: ...Annex 15 87 Program 2 ...
Страница 88: ...15 Annex 88 Program 3 ...
Страница 89: ...Annex 15 89 Program 4 ...
Страница 90: ...15 Annex 90 Program 5 ...
Страница 91: ...Annex 15 91 Program 6 ...
Страница 92: ...16 Notes 92 16 NOTES ...
Страница 93: ...Notes 16 93 ...