11
Maintenance schedule
80
Item
Procedure
Unscrew revision cover
Check BFP flap visually for damages, wear
and tightness
Open BFP flap by using the aggregate test
Position paper strip between hopper flange
and BFP flap and close BFP flap afterwards.
Try to pull out paper strip. If possible, adjust
BFP flap.
Conduct paper strip test at different positions
ID-fan
Unscrew 4x wing nut
Remove and clean ID-fan witch a brush
11.5
As needed
Item
Procedure
Chimney
Maintenance
respectively
Cleaning
and
inspection according to national standards
Fuel storage
room
Fuel storage room emptying (at least after 3
fillings) and check visually for damages and
wear (e.g.: stones, damaged walls,...). If the
fuel store is empty, lubricate any bearings and
bushings with a suitable lubricant