9
T-CONTROL
38
Term
Description
Unit
Menu "Settings"
Settings
1
Winter must
temperature
Setting up the winter must temperature (20-95). That´s the Buffer bottom
temperature, which will be provided during winter operation.
°C
Summer must
temperature
Setting up the summer must temperature (15-95). That´s the Buffer
temperature (Buffer bottom temperature- respectively if installed Buffer
centre temperature), which will be provided during summer operation.
°C
Difference
temperature
Setting up the temperature difference (-5 -25) between heat supplier (=
boiler) and buffer temperature bottom for excitation of the buffer loading
pump
°C
Switching
temperature
Indicates the switching temperature (10-35) (= average daytime
temperature). In general the switching temperature conduces to switch
between winter set temperature and summer set temperature.
°C
Temp. increase
Setting up the temperature increase (-25-15)of the required temperature.
▪
Due to heat losses a surcharge to the must temperature winter/summer
of the heating cicuit can be set.
°C
Balancing outside
sensor
Adjusting the balancing of the outside temperature (-5 to 5)
°C
Menu "Aggregate-Test"
Agg-Test
1
Buffer loading pump*
Indicates the state of the buffer loading pump:
▪
If the indicator lamp lights up, the buffer loading pump is activated and
the buffer gets charged.
Fastrun heating open
Indicates when fastrun heating is switched to OPEN.
Fastrun heating close
Indicates when fastrun heating is switched to CLOSE.
Menu "Barrier times"
Barrier times
1
Time 1
1 - 2 times can be set. The second time can be added by the +. Example:
▪
time 1:
08:00
– 10:00
▪
time 2:
15:00
– 21:00
-
08:00
– 11:00
Setting up individual buffer tank loading times of every weekday, when it
will be not heated
-
By pressing the symbol Monday preset gets assigned to remaining
weekdays.
-
Содержание firematic PELLET 120
Страница 1: ...OPERATING INSTRUCTIONS Wood chips pellets heating system firematic PELLET 120 201 ...
Страница 19: ...Temperature manager 8 19 Fig 8 6 Example temperature manager when time mode without difference ...
Страница 84: ...15 Annex 84 15 ANNEX 15 1 Additional boiler module Hydraulic recommendation 1 ...
Страница 85: ...Annex 15 85 Hydraulic recommendation 2 ...
Страница 86: ...15 Annex 86 15 2 Solar module Program 1 ...
Страница 87: ...Annex 15 87 Program 2 ...
Страница 88: ...15 Annex 88 Program 3 ...
Страница 89: ...Annex 15 89 Program 4 ...
Страница 90: ...15 Annex 90 Program 5 ...
Страница 91: ...Annex 15 91 Program 6 ...
Страница 92: ...16 Notes 92 16 NOTES ...
Страница 93: ...Notes 16 93 ...