
Heinzinger electronic GmbH
Phone: +49 (0) 8031 2458 0
www.heinzinger.com
Anton-Jakob-Str. 4, 83026 Rosenheim
Fax: + 49 (0) 8031 2458 58
Germany
Page 97
ERS COMPACT
3.11.15.4
Simulation mode
Apart from the panel technology there is also a simulation mode to select. Four options:
Mode
Description
U/I
Controllable simulation. Voltage (U
MPP
, in V) and current (I
MPP
, in A) in the maximum power point (MPP)
are variable during runtime. The purpose of this mode is to directly shift the MPP into various directions.
E/T
Controllable simulation. During runtime, the irradiation (E from german “Einstrahlung”, in W/m²) and
surface temperature (T, in °C) of the simulated solar panel are adjustable. This also impacts the curve
and the resulting MPP. The purpose of this mode is to analyse the impact of temperature and/or irra
-
diation on the performance of a solar panel.
DAY U/I
Automatic simulation run, processing a day trend curve consisting of up to 100,000 points defined by
values for U
MPP
, I
MPP
and time.
DAY E/T
Automatic simulation run, processing a day trend curve consisting of up to 100,000 points defined by
values for irradiation, temperature and time.
3.11.15.5
Day trend
The so-called day trend is a special simulation mode for long-term tests. It processes a curve consisting of up to
100,000 user-definable points. For every processed point on that curve, the PV curve is calculated anew.
Every point is defined by 3 values of which one is the dwell time. When defining long dwell times the day trend
curve can be supported by an interpolation feature which can be optionally activated. It will calculate and set in-
termediate points between two succeeding curve points. Hence it should be considered to run the day trend with
or without interpolation.
The day curve points have to be loaded into the device, either from a CSV file on USB stick or via digital interface.
The user selects the number of points according to the requirements of the simulation.
Formats of the CSV files to load from USB stick when manually configuring the function:
• For mode
DAY E/T
(required file name format: PV_DAY_ET_<arbitrary_text>.csv)
Column A =
Index
An ascending number between 1 and 100,000 (the first empty
index will cause the simulation to stop)
Column B
=
Irradiance
(E) in W/m²
Allowed range: 0...1500
Column C =
Temperature
(T) in °C
Allowed range: -40...80
Column D =
Dwell time
in milliseconds (ms)
Allowed range: 500...1.800.000
• For mode
DAY U/I
(required file name format: PV_DAY_UI_<arbitrary_text>.csv)
Attention! The values in columns B and C are real values which must not exceed the ratings of
the device or the device will neglect to load the file.
Column A =
Index
An ascending number between 1 and 100,000 (the first empty
index will cause the simulation to stop)
Column B
=
Voltage U
MPP
in V
Allowed range: 0...rated output voltage of the device
Column C =
Current I
MPP
in A
Allowed range: 0...rated output current of the device
Column D =
Dwell time
in milliseconds (ms)
Allowed range: 500...1.800.000
The number format and the column separator in the CSV files is determined by the regional
settings of the PC or the software used to create the files. The format must match the selection
for the device setting “USB file separator format” in the General Settings menu of the device,
else the device would neglect loading the file. For example, an american Excel should by default
use the dot as decimal separator and the comma as column separator, which would match the
selection “USB file separator format =
US
”.