HDG Bavaria GmbH 07/2008
HDG Compact 99 - 200 - Version 1 - en
6 Using the heating system – °C/QUANTITY menu
89
✎
See “Procedure” in this section.
I
NTEGRATING
THE
PEAK
LOAD
BOILER
This menu can be used to integrate an additional peak load boiler
using a third accumulator temperature sensor. The switch-on and
switch-off temperatures of the accumulator for the peak load boiler
are set here.
•
Temp. acc. top below
– If this temperature set for the upper accumulator sensor is not
met, the peak load boiler switches on.
•
Temp. acc. middle above
– If this temperature set for the middle accumulator sensor is ex-
ceeded, the peak load boiler switches off.
✎
See “Procedure” in this section.
Temperature adjustment using the accumulator sensors is only
available if the boiler activation is set to “Accumulator temperature
sensor”.
✎
See section “6.6 ON/OFF menu”, under “Selecting and setting
boiler activation”.
Boiler on/off
2-06
On: Temp. acc. top below
70 / 58°C
Off: Temp. acc. bottom above
65 / 51°C
END
The standard setting for the boiler switch-on temperature for
Temp. acc. top below
is 70 °C.
The standard setting for the boiler switch-off temperature for
Temp. acc. bottom above
is 65 ?.
This is an optional submenu and only available with double heating
systems (if necessary, also with oil/gas boilers).
Peak load boiler
2-07
On: Temp. acc. top below
55 / 68°C
Off: Temp. acc. middle above
65 / 65°C
END