6 Using the heating system – SERVICE menu
114
HDG Compact 99 - 200 - Version 1 - en
©
HDG Bavaria GmbH 07/2008
✎
See “Procedure” in this section.
U
NDERPRESSURE
CONTROL
•
Negative pressure limit
– If this set value is not met, the boiler switches to "Burn out".
•
Positive pressure limit
– If this set value is exceeded, the boiler is stopped as with an
"Emergency stop".
•
Delay grate pressure switch
– The response time of the pressure switch can be set.
•
Vacuum fan rotational speed uncontrolled
– When the underpressure control is deactivated (parameter
1-
08
), the flue gas fan runs at the set speed.
✎
See “Procedure” in this section.
S
ETTING
CHIMNEY
SWEEP
TEST
•
Enabling boiler temperature
– After this set boiler temperature is exceeded, the chimney
sweep test is enabled.
•
Enabling combustion chamber temperature
– After this set combustion chamber temperature is exceeded,
the chimney sweep test is enabled.
Flue gas temperature
5-13
Cleaning system start
:
220 / 50 °C
Maximum flue gas temperature:
250 / 50 °C
Fault delay
:
1.0 m
Incline
:
2
END
Underpressure control settings
5-14
Underpressure limit
: -350 /-377 pa
Overpressure limit
:
10 /-377 pa
Delay Grate pressure switch :
5.0 / 0.7 m
Vacuum fan speed uncontr.
:
90 %
END