SupervisorMode
WTX120
A4500-1.1
HBM: public
95
10.2.11
Alarm:Empty
As soon as one of the alarms is set to
On
, the alarm in question is active. If
none of the alarms is indicating an error, the alarm status is cleared (“0”). If at
least one of the alarms is indicating an error, the alarm status is set (“1”). If a
digital output (Alarm) has been configured, it is set or reset according to the
alarm status.
Menu
Key
Function/Secondary selection
Alarm:Empty
Empty Off/On
Monitoring of the empty
weight at the start of dosing
(
)
Flow monitor Off/On
Activate the alarm for fill flow
monitoring (
see also chapter
and chapter
)
Overflow Off/On
Alarm in case of over/under
flow of gross signal, net signal
or ADC value
Dos.time Off/On
Alarm in case of exceeding
the maximum dosing time
(
)
Container Off/On
Alarm in case of deduction
weighing and gross measured
value < empty weight or gross
measured value < target
weight
Min.start Off/On