hydroSpider2 User’s Manual v1.23
Page 72
5.17
Advanced Settings
The Advanced page provides various settings which change the default behaviour of the
hydroSpider2. To access the
Change Advanced Settings
page, click the
Advanced
link from the
Change Setup
page. This will bring you to the following page:
The
When Entering Change Setup
setting determines whether controls are turned off or not
when setup is entered.
By default, all controls are turned to the ‘Off’ position when
Change Setup
is entered.
Changing this option is useful if you want to keep the state of your controls while you
browse the Change Setup pages.
Minimum Alarm Auto Ack Time
: By default, 60 minutes is the minimum value that an
alarm’s Auto Acknowledgement time can be set to. Changing this setting allows you to then
set up alarms with auto acknowledgement times of as low as 5 minutes.
Lowering this setting is useful if you want the hydroSpider to send out more alerts on alarms
triggering off fast-changing inputs.
See 5.10 - Alarms for more information on alarms and auto acknowledgement.
Note
: If you are using a hydroSpider2 with the LiveSMS option enabled, you will also see a LiveSMS
Settings section on this page – see Appendix E - LiveSMS (Software Option) for details.
Note
: If you are using a SDI-12 / RS-485 hydroSpider, you will also see a Modbus-485 Settings section
on this page – see Appendix A - SDI-12 / RS-485 for more information.