Page 9
Programmable Energy Saver Modules
Programmable Energy Saver Modules may be connected to:
Lumina Controller:
Zone 9 and Output 1
through
Zone 16 and Output 16, respectively
1.
Lumina can support up to 8 Programmable Energy Saver Modules (PESM). Each PESM requires one zone input and one
controller output. The zone input corresponds to the controller output (Zone 9 and Output 1 through Zone 16 and Output 8,
respectively). If Zone 9 is used, Output 1 must be used as its pair.
2.
When setup as an Energy Saver Zone Type (Type 80), the zone and unit (output) is used as a pair to read in temperature and
control the setback temperature of the house. Only zones 9-16 may be configured as an Energy Saver zone.
3.
Run a 4-conductor wire from the Lumina controller to each PESM.
4.
The PESM should be mounted on an interior wall, preferably close to the HVAC thermostat. Run a 2-conductor wire from
the PESM to the thermostat. Connect the PESM between the RED wire going to the thermostat and the RED terminal on the
thermostat.
5.
Program the zone type for PESMs as a Type 80, Energy Saver. It may also be programmed as a Temperature (Type 82), or
Temperature Alarm (Type 83) for special applications.
NOTES ON HVAC SYSTEMS
1.
Description of the PESM
The PESM is a temperature sensor and control relay in a small enclosure that mounts near a central heating, ventilation, and
air conditioning (HVAC) system thermostat. The PESM allows the automation system to read the temperature of the area
that the HVAC system controls. The relay in the PESM is used to break the 24V RED wire between the thermostat and the
HVAC system. When the automation system is in setback mode and the actual temperature is between the LO and HI
setpoints, the relay energizes to break the 24V red wire; hence, the HVAC system will no longer operate.
In heating season, when the actual temperature falls below the LOW setpoint, the automation system turns the relay in the
PESM off, thus restoring power to the thermostat, allowing the thermostat to heat as it normally would under the control of
the thermostat. The PESM will cycle the thermostat on and off to maintain the LOW setpoint.
In cooling season, when the actual temperature rises above the HI setpoint, the automation system turns the relay in the
PESM off and the thermostat will cool as it normally would under the control of the thermostat. The PESM will cycle the
thermostat on and off to maintain the HI setpoint.
The Red LED on the PESM will illuminate when the PESM is overriding the thermostat. The Red LED will be off when the
thermostat is working normally.
If the PESM is disconnected from the automation system, the relay will not energize and the HVAC system will operate
normally, under the control of the thermostat.
2.
Standard Heating and Cooling Systems
The PESM is compatible with all mechanical thermostats.
3.
The PESM is also compatible with electronic thermostats that run totally on battery power.
4.
Heat Pumps
Programmable Energy Saver Modules are compatible with heat pumps, however, the savings gained by setting the heat pump
back may be erased by the auxiliary heaters when the heat pump tries to recover from the setback. A PESM will work best
with heat pumps that have one or more of the following features:
Содержание lumina
Страница 2: ...Copyright 2001 2006 Home Automation Inc All Rights Reserved...
Страница 113: ...Page 105 CODE DESCRIPTION 546 WINE 252 WING 547 WINTER 548 WOOD CODE DESCRIPTION 549 WORK 253 YARD 550 YOU 190 ZONE...
Страница 114: ......
Страница 115: ......
Страница 116: ...HAI New Orleans LA U S A...