APS-7000 Programming Manual
70
:SYSTem:ERRor:ENABle .......................................... 83
:SYSTem:KLOCk ....................................................... 84
:SYSTem:REBoot ........................................................ 84
:SYSTem:WRELease .................................................. 84
:SYSTem:BEEPer:STATe
Set
Query
Description
Sets or queries the buzzer state on/off.
Syntax
Query Syntax
:SYSTem:BEEPer:STATe {<bool>|OFF|ON}
:SYSTem:BEEPer:STATe?
Parameter
OFF | 0
Turns the buzzer off.
ON | 1
Turns the buzzer on.
Return parameter <bool>
Returns the buzzer status.
:SYSTem:COMMunicate:GPIB[:SELF]
:ADDRess
Set
Query
Description
Sets or queries the GPIB address.
Note:
The setting will only be valid after the power has
been cycled.
Syntax
Query Syntax
:SYSTem:COMMunicate:GPIB[:SELF]:ADDRess
<NR1>
:SYSTem:COMMunicate:GPIB[:SELF]:ADDRess?
Parameter/Return <NR1>
0~30
Example
SYST:COMM:GPIB:ADDR 15
Sets the GPIB address to 15.
:SYSTem:COMMunicate:LAN:DHCP
Set
Query
Description
Turns DHCP on/off. Queries the DHCP status.
Note:
The setting will only be valid after the power has
been cycled.
All manuals and user guides at all-guides.com