GST102A/GST104A/GST108A/GST116A
Conventional Fire Alarm Control Panel
Installation and Operation Manual
Page
3
Chapter 1 Product Overview
GST102A/104A/108A/116A Conventional Fire Alarm Control Panel is designed in compliance with
EN 54-2. It’s compatible with GST C-9403 Conventional Sounder Strobe designed by EN 54-3, C-
9103 Conventional Rate of Rise and Fixed Temperature Heat Detector by EN 54-5, C-9102
Conventional Photoelectric Smoke Detector by EN 54-7, and DC-9204 Conventional Manual Call
Point by EN 54-11. The panel is easy to install and operate. Control functions are enabled by a key
switch. Programming functions are enabled by a key switch and an internal switch.
This series of panels are basically the same in application and operation, their only main differences
being the amount of zones and the size of the cabinets, see table 1-1.
Table 1-1
FACP
Number of Detection
Zones
Number of Sounder
Outputs
GST102A
2
3
GST104A
4
3
GST108A
8
3
GST116A
16
3
1.1
Features
Supports up to 16 detection zones, with conventional detectors and manual call points;
the maximum number of external conventional points per zone is 32.
Three sounder outputs, one alarm output, one fault output and one disable/supervisory
output.
Able to report short and open circuits of zones, sounder outputs and alarm output.
Test and disable functions
Programmable on manual call point connection, sound modes, sounder delay modes and
output delay modes.
Three access levels settable via the key switch and the internal switch.
Reserved repeater panel interface for fire alarm indication of multiple zones.
Designed with standby batteries and space provision for two sealed lead-acid batteries.
The maximum number of points per CIE as shown in Table 1-2.
FACP
GST102A
GST104A
GST108A
GST116A
Max points
≤
64
≤
128
≤
256
<512
1.2
Technical Specifications
1.2.1
Operating Voltage
Input Voltage: 220V/230VAC
+10%
-15%
Frequency: 50/60Hz
Input Current: 0.8 A
Fuse: 250VAC, T2A in SPS
Recommended Wiring: 1.5mm
2
or above of shield cable, complying with local installation
code.