GST102A/GST104A/GST108A/GST116A
Conventional Fire Alarm Control Panel
Installation and Operation Manual
Page
25
Two sounder patterns are shown in Table 3-7. Default setting is Continuous Output
Table 3-7
Sounder Patterns
“5” of SW3
(
SOUNDER MODE
)
Pulse Output
ON
Continuous Output
OFF (Default)
Delay time can be obtained as shown in Table 3-8. Default setting is 0 seconds
Table 3-8
Delay (s)
“1” to “4” of SW3 (
DELAY TIME
)
1
2
3
4
0
OFF
OFF
OFF
OFF
10
ON
OFF
OFF
OFF
20
OFF
ON
OFF
OFF
30
ON
ON
OFF
OFF
40
OFF
OFF
ON
OFF
50
ON
OFF
ON
OFF
60
OFF
ON
ON
OFF
70
ON
ON
ON
OFF
80
OFF
OFF
OFF
ON
90
ON
OFF
OFF
ON
100
OFF
ON
OFF
ON
110
ON
ON
OFF
ON
120
OFF
OFF
ON
ON
130
ON
OFF
ON
ON
140
OFF
ON
ON
ON
150
ON
ON
ON
ON