GST102A/GST104A/GST108A/GST116A
Conventional Fire Alarm Control Panel
Installation and Operation Manual
Page
16
2.2
Mains Connection
The CIE is powered by 220/230VAC. It
’s recommended to use 1.5mm
2
or above shield cable,
subject to local installation codes.
The incoming power cable ground (Green/Yellow) wire should be connected to terming G and be
reliably grounded. Connect the neutral (Blue) wire to terminal N and connect the Live (Brown) wire
to terminal L. See the Fig. 2.2.
L
N
N
G
N
Fig. 2-2
Note:
➢
The power cables shall be fixed to the enclosure using a restraint clamp for strain relief.
➢
Do not power the system until the installation is completed.
2.3
Battery Connection
Connect the batteries as in Fig. 2-3 and then to the battery terminal XT2 on the control board.
BATTERY
BATTERY
RED
BLACK
FUSE F5A/250V
Fig. 2-3
☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆
Note:
➢
Refer to Chapter 5 for Calculation of Batteries.
➢
Do not make battery connections until the installation is completed.
➢
The fuse of the batteries may be broken if the polarity is connected incorrectly.
☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆