GST102A/GST104A/GST108A/GST116A
Conventional Fire Alarm Control Panel
Installation and Operation Manual
Page
27
3.7
Setting Auxiliary Functions
RESOUND MODE: When the “6” of SW2 (
RESOUND MODE
) is set to the ON position,
resound mode is turned on. When there is fire alarm from a zone, the sounder outputs
associated to this zone will be started. Pressing
SILENCE/RESOUND ALARM
key and these
sounder outputs can be silenced; if there is an alarm signal from another zone at this moment,
the silenced sounder outputs that are not associated to this new alarm zone will resound. If
resound mode is turned off, the silenced sounder outputs not associated to this new alarm
zone will remain silenced. Default setting is ON.
SILENCE RESET MODE: When the “7” of SW2 (
SIL-RESET MODE
) is set to the ON position,
silence-reset mode is turned on. When there is fire alarm from a zone and its associated
sounder outputs are started, the CIE will not be reset until the sounder outputs are silenced. If
silence-reset mode is turned off, the CIE can be reset immediately. Default setting is ON.
SILENCE DELAY MODE: When the “8” of SW2 (
SIL-DEALY MODE
) is set to the ON position,
silence-delay mode is turned on. When there is fire alarm from a zone and its associated
sounder outputs are started, the CIE has to stay in fire condition for 3 minutes before the
sounder outputs could be silenced. If silence-delay mode is turned off, the sounder outputs
can be silenced immediately. Default setting is OFF.
DISABLE/SUPERVISED OUTPUT MODE: When the “6” of SW3 (
DIS. / SUP. OUT
) is set to
the OFF position, the disable/supervised relay output is set for disable output; otherwise, this
output is set for supervised output. Default setting is OFF.
RELAY OUTPUT MODE: When the “7” of SW3 (
RELAY OUTPUT
) is set to the OFF position,
the FAULT1 to FAULT16 on relay board are defaulted as fault outputs. When the “7” of SW3
(
RELAY OUTPUT
) of is set to the ON position, FAULT1 to FAULT16 on relay board are set to
general fire trips, which all will activate on any zone fire alarm. Default setting is OFF.
☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆
Note: The auxiliary function has not been tested in EN54-2/4.
☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆
3.8
Ground Fault Detection
The CIE can detect a ground fault by connecting the X6(
EARTH FAULT
) with a jumper. Otherwise,
the CIE does not detect a ground fault.
3.9
Auxiliary Power Setting
Shorting “24V” and “AUX” of X3 with a jumper, the
AUX SUPPLY
output will be constant. If shorting
“AUX” and “LOOP” of X3, the
AUX SUPPLY
output will drop for about 10 seconds when the CIE is
reset.