GST102A/GST104A/GST108A/GST116A
Conventional Fire Alarm Control Panel
Installation and Operation Manual
Page
19
Table 3-5
Output
Normally
closed contact
Normally open
contact
Voltage output
DO NOT
CHANGE
JUMPER
SETTINGS
WITH
POWER
STILL
CONNECTED
Alarm
output:
Link pins
1 & 2,
and
3 & 4
of
X1
as shown
Link pins
1 & 2,
and
4 & 5
of
X1
as shown
(Default)
Link pins
2 & 3
and
5 & 6
of
X1
as shown
Sounder
output 1:
Link pins
1 & 2,
and
3 & 4
of
X2
as shown
Link pins
1 & 2,
and
4 & 5
of
X2
as shown
Link pins
2 & 3
and
5 & 6
of
X2
as shown
(Default)
X1
X2
Fig. 5
3.3
Disablement of a Zone or Output
3.3.1
Use of Disablement Function
In case there is any fault with a detection zone or a sounder/alarm output, it can be disabled so that
it does not affect normal operation of other zones. After the fault is removed, the disabled detection
zone or output can be enabled again. This operation applies to the 16 detection zones, 3 sounder
outputs, and 1 fire alarm output.