Chapter 4 Operation Instructions
4.1
Working State Description
4.1.1
State of Detection Zones
Normal: If a zone is in normal condition, the zones’ red and amber LEDs are off, only the power
LED (green) is on.
Fire: If there is a zone in fire condition,
FIRE
LED and zone red LED flash. In access level II,
pressing the
SILENCE BUZZER
button, they will illuminate steadily.
Supervisory: non-activated supervisory zone green LED illuminates. Activated supervisory
zone SUPERVISED LED flash. In access level II, pressing
SILENCE BUZZER
key,
SUPERVISED
LED illuminate steadily. (Default settings)
Fault: If there is a zone in fault condition,
FAULT
LED and zone amber LED flash. In access
level I, pressing the
SILENCE BUZZER
button,
FAULT
LED illuminates steadily and zone
amber LED remains flashing.
Disabled: If there is a zone disabled,
DISABLE
LED and zone amber LED illuminate steadily.
4.1.2
Alarm Output State
Normal: If alarm output is in normal condition,
ALARM ROUTING ACTIVATED LED and
ALARM OUTPUT FAULT
LED should be off.
Fire: If the alarm output is activated,
ALARM ROUTING ACTIVATED
LED illuminates steadily.
Fault: If the alarm output is in fault condition,
FAULT
LED and
ALARM OUTPUT FAULT
LED
flash. In access level I, pressing the
SILENCE BUZZER
button,
FAULT
LED illuminates
steadily,
ALARM OUTPUT FAULT
LED remains flashing.
4.1.3
Sounder Outputs State
Normal: If a sounder output is in normal condition,
SOUNDER X FLT/DIS
LED should be off.
Fault: If there is a fault with any of the sounders,
FAULT
LED and
SOUNDER X FLT/DIS
LED
flash. In access level I, pressing the
SILENCE BUZZER
button,
FAULT
LED illuminates
steadily and
SOUNDER X FLT/DIS
LED remains flashing.
Disabled: If any of the three sounder outputs are disabled,
DISABLE
LED and
SOUNDER X
FLT/DIS LED
illuminate steadily.
4.1.4
Safe State
When there is a fault with any CPU that makes the CIE unable to work properly or changes system
data, the CIE will enter safe state.
FAULT
and
SYSTEM FAULT
LED illuminate.
The buzzer sounds continuously.
The keypad cannot be operated.
The CIE cannot monitor fire.
Fault output is activated.
Other outputs remain the same before the CIE enters safe state.
Other indicators remain the same before the CIE enters safe state.
☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆
Note: Safe state can only be cleared by re-powering the CIE.
☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆