GST102A/GST104A/GST108A/GST116A
Conventional Fire Alarm Control Panel
Installation and Operation Manual
Page
28
3.10
Restore Default Settings
The basic features of the default settings are as follows:
Every zone is set “With Manual Call Point”.
When there is fire alarm from any zone, all sounder outputs will be started, and these outputs
will be continuous and not be delayed.
The alarm output is not set with delay time.
All zones and sounder outputs are not disabled.
A quick way to restore default settings as follows:
1
Enter access level III.
2
Pressing the
OUTPUT PROGRAM
button for at least 2 seconds, the CIE gives 1 second sound
indication to indicate a successful reset to factory settings.
3
Exit access level III.
3.11
Default DIP Switch Settings
Label
Setting
Alarm output
N/O
Sounder 1 Output
Voltage
Aux Power
Jumper pins on AUX + 24 for continuous
voltage
Ground Fault
connected
Level 3
1
off
MCP zone
2
off
Alarm output
3
off
sounder output
4
off
sounder mode
5
off
resound mode
6
off
sil-reset mode
7
off
sil-delay mode
8
off
Delay time 1
1
off
Delay time 2
2
off
Delay time 3
3
off
Delay time 4
4
off
test zone out
5
off
dis/sup. Out
6
off
Relay output
7
off
reserve use
8
off
SW3
Location
X1
X2
X3
X6
SW2