GST102A/GST104A/GST108A/GST116A
Conventional Fire Alarm Control Panel
Installation and Operation Manual
Page
7
BATTERY FAULT:
Yellow. It flashes when there is battery fault and illuminates steadily
when the fault sound is silenced.
CHARGER FAULT:
Yellow. It flashes when there is charger fault and illuminates steadily
after the fault sound is silenced.
EARTH FAULT:
Yellow. It flashes when any cable of sounder output (voltage contact),
alarm routing output, auxiliary power output or zone input, connects with the enclosure of
the panel. It illuminates steadily when the fault sound is silenced.
SYSTEM FAULT:
Yellow. It illuminates steadily when the CPU is in fault condition or CPU
communication is abnormal.
DELAY MODE:
Yellow. It flashes when there is an alarm output or sounder output in
delayed condition.
BUZZER MUTE:
Yellow. It illuminates steadily when the buzzer is silenced.
SILENCE:
Yellow. It
illuminates steadily when the sounders are silenced.
SOUNDER 1 FLT/DIS:
Yellow. It flashes when Sounder 1 output is in fault condition, and
it illuminates steadily when Sounder 1 output is disabled.
SOUNDER 2 FLT/DIS:
Yellow. It flashes when Sounder 2 output is in fault condition, and
it illuminates steadily when Sounder 2 output is disabled.
SOUNDER 3 FLT/DIS:
Yellow. It flashes when Sounder 3 output is in fault condition, and
it illuminates steadily when Sounder 3 output is disabled.
ALARM OUTPUT FAULT:
Yellow. It flashes when alarm output is in fault condition, and it
illuminates steadily when Alarm output is disabled.
1.3.2
Zone Status Indicators
ZONE RED LED:
Red. It flashes when a zone is in fire condition
(
0.5
:
0.5
)
. And it
illuminates steadily after Mute/ACK is pressed.
ZONE AMBER LED:
Yellow. It flashes when the zone is in fault condition
(
0.5
:
0.5
)
. And
it illuminates steadily when the zone is disabled or in test mode.
ZONE SUPERVISED LED
(
Z1~Z16
)
: It illuminates GREEN when the zone is defined
as a supervisory type. (Factory Default, refer to Chapter 3.6.2 for programming
instructions). This feature is typically used for pump running and pump stopped
indications.
1.3.3
Operating Indicators and Keys
Keys
➢
SILENCE BUZZER:
In Access Level I and access level II, fault sound, supervisory
sound, and an alarm sound can be silenced.
➢
SILENCE/RESOUND ALARM:
Pressing this key can silence all the sounders outputs;
pressing it again in fire condition, the silenced sounders output will be activated again.
The LED illuminates yellow steadily when the sounders are silenced.
➢
RESET:
It is available in Access Level II for resetting the control panel.
➢
DISABLE:
It is
available in Access Level II. Pressing this key can disable all zones
with a fire condition. Note: The warning system must first be silenced in order for this
button to operate.
➢
DIS/ENABLE WARNING SYSTEM:
It is available in Access Level II. Pressing this
key can disable/enable all sounder outputs.
➢
SCROLL:
It
is available in Access Level II for scrolling to choose.
➢
CANCEL:
It
is available in Access Level II for cancellation.