GST102A/GST104A/GST108A/GST116A
Conventional Fire Alarm Control Panel
Installation and Operation Manual
Page
26
3.6
Supervisory Mode
3.6.1
Use of Supervisory Function
Zones can be defined as supervisory for monitoring field device status.
☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆
Note: Supervisory setting will be saved even if the CIE is powered off.
Note: Supervisory function has not been tested for EN54-2.
☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆
3.6.2
Programming a Zone to Supervisory
1
Enter access level III.
2
Set the “8” of SW3 (
RESERVE USE
) on control board to ON position.
3
Pressing the
OUTPUT PROGRAM
button,
OUTPUT PROGRAM
LED illuminates steadily and
the green LED of zone 1 starts flashing to show zone 1 is to be selected for supervisory setup.
SUPERVISED LED and SOUNDER 1 FLT/DIS flashes. The
FAULT
LED will indicate according
to the CIE fault condition. Other indicators, except for the above mentioned LEDs, will be
turned off.
4
Pressing the
SCROLL
button can toggle between zones 1 to 16. Flashing Green zone LED
indicates the selected zone. A steady illuminating green zone LED indicates the zone is already
defined as a supervised.
5
Pressing the
TEST
button can switch among the LED indicators Sounder 1, Sounder 2,
Sounder 3 and Alarm Output. options as shown in table 3-9
Table 3-9
LED ON
LED FLASHING/OFF
Sounder 1:
MODE
AUTO RESET
LATCHED
Sounder 2:
BUZZER
OFF
ON
Sounder 3:
Green LED
LED OFF
LED ON
Alarm Output:
DELAY
12 SEC DELAY
INSTANTLY
6
Pressing the
DISABLE/ENABLE
button to turn LED ON or OFF of selected indicator. Default
setting are all LED’s are OFF.
7
Pressing the
ENTER
button to set the zone as supervised with programming logic or cancel
existing supervised zone logic, and the CIE will give 1 second sound indication. Repeat step
4 to 7 to set another zone as supervised.
8
Pressing the
CANCEL
button exits supervisory setting status and
OUTPUT PROGRAM
LED
turns off.
9
Set the “8” of SW3 (
RESERVE USE
) on control board to OFF position.
10
Exit access level III.