GST102A/GST104A/GST108A/GST116A
Conventional Fire Alarm Control Panel
Installation and Operation Manual
Page
22
3.4.3
Test zone output mode
TEST ZONE OUTPUT MODE: When the “5” of SW3 (TEST ZONE OUT) is set to the ON
position, test zone output mode is turned on. When a zone is in test mode and there is an alarm
signal, coming from the zone, the sounder outputs associated to the zone will be automatically
activated for 5 seconds. If test zone output mode is turned off, the sounder outputs will not be
activated. Default setting is OFF.
3.5
Programming Output Modes
All output settings programming has to be done under Access Level III. So before programming the
Outputs, please first enter Access Level III according to the instructions in Section 3.1.3.
The CIE can be programmed through keypad for the functions below:
Setting a zone “With Manual Call Point”. If a zone is set “With Manual Call Point”, a fire alarm
from the zone will activate its associated sounder outputs and alarm output, regardless of
whether the zone is set with delayed output or not;
Associating a zone with sounder outputs. The output mode, sound pattern, and delay time of
the sounders associated to the zone can be set respectively.
Setting delay time for alarm output.
3.5.1
Setting Zone “With Manual Call Point”
If a zone is set “With Manual Call Point”, any fire alarm coming from that zone (either from a detector
or a manual call point), the CIE will immediately alarm and activate all sounders associated to that
zone and the alarm output regardless of any delay setting. Basic steps are shown below.
1
Enter access level III.
2
Set the “2” of SW2 (
MCP ZONE
) on control board to ON position.
3
Pressing the
OUTPUT PROGRAM
button, the
OUTPUT PROGRAM
LED illuminates
steadily and the amber LED of zone 1 flashes to show zone 1 is to be selected for “With
Manual Call Point” setup. And DELAY MODE led flashes. The
FAULT
LED will indicate
according to the CIE fault condition. Other indicators, except for the above mentioned LEDs,
will be turned off.
4
Pressing the
SCROLL
button toggles between zones 1 to 16.
5
The amber
LED for zone 1 to 16 will flash when the zone is selected. Pressing the
ENTER
button can
choose whether or not to program the zone as “With Manual Call Point” and the
CIE will give 1 second sound indication. The amber zone LED illuminates steadily to
indicate the zone is NOT programmed as “With Manual Call Point”.
6
Pressing the
CANCEL
button exits the programming mode and the
OUTPUT PROGRAM
LED will be turned off.
7
Set the “2” of SW2 (
MCP ZONE
) to OFF position.
8
Exit access level III.