Nexans NX 200 and 200 Plus (LPCB tested)
Prysmian FP 200 and 200 Gold
Draka Firetuf and Firetuf Plus
And all LPCB approved Fire cables
Recommended Cable Length ≤3000m
2.4 Detection Loop Parameters
LOOP OUT (O+, O-): Polarized signal cable from the FACP connecting up to 242
addressable devices through maximum 8 loops.
LOOP IN (I+, I-): Polarized signal cable returning to the FACP.
Output Voltage: 21V~27V pulse
Output Current: 0mA~300mA
Type of Loop: Class A loop
Recommended Wiring (subject to local installation codes):
GST fire cable
Vencroft Gold and Platignum
Nexans NX 200 and 200 Plus (LPCB tested)
Prysmian FP 200 and 200 Gold
Draka Firetuf and Firetuf Plus
And all LPCB approved Fire cables
Recommended Cable Length
≤1000m
2.5 Input/Output Loop Parameters
Recommended Wiring (subject to local installation codes):
GST fire cable
Vencroft Gold and Platignum
Nexans NX 200 and 200 Plus (LPCB tested)
Prysmian FP 200 and 200 Gold
Draka Firetuf and Firetuf Plus
And all LPCB approved Fire cables
Recommended cable length
≤1000m
2.5.1 ALARM ROUTING (+, -)
Output Voltage: 21VDC ~27VDC
Output Current: 0mA~200mA
End of Line Resistor: 4.7kΩ
2.5.2 FEED BACK (F1, F2)
End of Line Resistor: 4.7k
Ω
2.5.3 OUTPUT TO F.P.E. (+, -)
Output Voltage: 21VDC~27VDC
Output Current: 0mA~200mA
End of Line Resistor: 4.7k
Ω
2.5.4 OUTPUT TO SOUNDER (+, -)
Output Voltage: 21VDC~27VDC